900 MCM XHHW-2 Aluminum Building Wire 600V
Where are we? 4 Continents 9 Countries

Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Quick Support
900 MCM XHHW-2 Aluminum Building Wire 600V
Allowable Ampacity for 900 MCM XHHW-2 Aluminum Cable 600V at 75°C: 425 Amps
Allowable Ampacity for 900 MCM XHHW-2 Aluminum Cable 600V at 90°C: 480 Amps
900 MCM aluminum XHHW-2 is single-conductor building wire with cross-linked polyethylene (XLPE) insulation, made to be installed in conduit or other raceways. It's rated for wet and dry locations at up to 90°C and 600V.
Applications:
900 MCM aluminum XHHW-2 is installed in conduit and other NEC-recognized raceways for services, feeders, and branch circuits, in wet or dry locations at up to 600V. It's rated 425A at 75°C and 480A at 90°C. Typical uses:
-
400A feeders at full rating in a single run
-
800A services run as two parallel sets
-
1200A services run as three parallel sets
-
Transformer secondaries and switchgear connections
Also Known As:
900 xhhw-2 cable, 900 hxxw-2 cable, 900 rw90 cable, 900 rw90 wire, 900 type xhhw-2, 900 xhhw-2, 900 southwire xhhw-2, 900 xhhw-2 insulation, xhhw-2 aluminum wire, 900 mcm aluminum wire
900 MCM XHHW-2 Aluminum Data Center Applications
In data centers, 900 MCM aluminum XHHW-2 is used for long service and generator feeders, where its lower cost and weight add up across paralleled sets. Data center loads run continuously, so NEC 215.2 sizes feeders at 125% of the load unless the breaker is 100% rated. Terminations must be rated for aluminum.
-
Two parallel sets for 800A feeders
-
Three parallel sets for 1200A service feeders from the utility transformer
-
Generator feeders where long runs make copper costly
Standards:
-
XHHW-2 meet or exceed the following standards:
-
UL standard 44
-
Requirements of the National Electrical Code
-
ASTM standards B 800, B 801
-
Federal Specification J–C-30B
-
Sunlight resistant
Construction
Conductors:
Compact bare AA-8000 series aluminum alloy, Class B stranded per ASTM
Insulation:
XHHW-2 has abrasion, heat, and moisture resistant cross-linked polyethylene insulation. Cross linking a polyethylene helps to achieve an excellent strength that makes the material suitable for covering this cable used in harsh conditions.
Specifications:
-
Size AWG: 900 MCM
-
Stranding: 58
-
Conductor Diameter Inches: 0.999
-
Insulation Thickness Inches: 0.080
-
O.D. Inches: 1.159
-
New Weight lb/1000FT: 966 lbs
-
Ampacity at 75°C: 425 Amps
-
Ampacity at 90°C: 480 Amps
|
Compatible with Manufacturer |
|
| Houston item : |
Black : HW002A90001 Black : 900-01XHHWBLACKAL |
| Priority Wire & Cable : | Black : 900-01XHHW-2-ALUM |
| Southwire : |
Black : 55405999 Orange : 56044699 Yellow : 56044799 Brown : 56044599 Gray : 56044899 |
FAQ's
What is 900 MCM aluminum XHHW-2 used for?
What are the main differences between XHHW and XHHW-2 wires?
What is the difference between THHN and XHHW-2 wire?