250 MCM XHHW-2 Aluminum Building Wire 600V
Where are we? 4 Continents 9 Countries

Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Quick Support
250 MCM XHHW-2 Aluminum Building Wire 600V
Allowable Ampacity for 250 MCM XHHW-2 Aluminum Cable 600V at 75°C: 205 Amps
Allowable Ampacity for 250 MCM XHHW-2 Aluminum Cable 600V at 90°C: 230 Amps
250 MCM aluminum XHHW-2 is single-conductor building wire with cross-linked polyethylene (XLPE) insulation, made to be installed in conduit or other raceways. It's rated for wet and dry locations at up to 90°C and 600V.
Applications:
250 MCM aluminum XHHW-2 is installed in conduit and other NEC-recognized raceways for services, feeders, and branch circuits, in wet or dry locations at up to 600V. It's rated 205A at 75°C and 230A at 90°C. Typical uses:
- 200A services and feeders at full rating in commercial and other non-dwelling installations
- 225A home services under NEC 310.12
- 400A services run as two parallel sets
- 200A generator and transfer switch feeders
- Busbars and power distribution
- Renewable energy installations
- Backup generators
Also Known As:
250 mcm aluminum wire, 250 kcmil aluminum wire, 250 xhhw-2 cable, 250 hxxw-2 cable, 250 rw90 cable, 250 rw90 wire, 250 type se cable style u type xhhw-2, 250 xhhw-2, 250 southwire xhhw-2, 250 xhhw-2 insulation, 250 aluminum wire, xhhw-2 aluminum wire, 250 mcm aluminum, 200 amp wire, 200 amp cable
Standards:
- XHHW-2 meet or exceed the following standards:
- UL standard 44
- Requirements of the National Electrical Code
- ASTM standards B 800, B 801
- Federal Specification J–C-30B
- Sunlight resistant
Construction
Conductors:
Compact bare AA-8000 series aluminum alloy, Class B stranded per ASTM
Insulation:
XHHW-2 has abrasion, heat, and moisture resistant cross-linked polyethylene insulation. Cross linking a polyethylene helps to achieve an excellent strength that makes the material suitable for covering this cable used in harsh conditions.
Specifications:
- Size AWG: 250 MCM
- Stranding: 35
- Conductor Diameter Inches: 0.520
- Insulation Thickness Inches: 0.065
- O.D. Inches: 0.650
- New Weight lb/1000FT: 288 lbs
- Ampacity at 75°C: 205 Amps
- Ampacity at 90°C: 230 Amps
|
Compatible with Manufacturer |
|
| Houston item : |
Black : HW002A25001 Black : 250-01XHHWBLACKAL |
| Priority Wire & Cable : | Black : 250-01XHHW-2-ALUM |
| Omni Cable item : |
Black : M8250ST-01 Blue : M8250ST-05 Green : M8250ST-04 Orange : M8250ST-07 Red : M8250ST-03 White : M8250ST-02 Yellow : M8250ST-08 Brown : M8250ST-010 Gray : M8250ST-06 |
| Southwire : |
Black : 27834101 Blue : 57639199 Green : 56744099 Orange : 57638699 Red : 57639099 White : 57639201 Yellow : 57638799 Brown : 57638599 Gray : 57638899 |
FAQ's
What is 250 MCM aluminum XHHW-2 used for?
What are the main differences between XHHW and XHHW-2 wires?
What is the difference between THHN and XHHW-2 wire?
Is 250 MCM aluminum XHHW-2 rated for a 200 amp service?
Can XHHW-2 wire be buried underground?
Does XHHW-2 wire have to be run in conduit?
Is XHHW-2 wire sunlight resistant?
Can XHHW-2 wire be used in cold weather?
Call Us: 1-516-482-6313 Text Us: 1-516-703-3460
Garrie AI: Your Cable Guide