700 MCM XHHW-2 Aluminum Building Wire 600V
Where are we? 4 Continents 9 Countries

Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Quick Support
700 MCM XHHW-2 Aluminum Building Wire 600V
Allowable Ampacity for 700 MCM XHHW-2 Aluminum Cable 600V at 75°C: 375 Amps
Allowable Ampacity for 700 MCM XHHW-2 Aluminum Cable 600V at 90°C: 425 Amps
700 MCM aluminum XHHW-2 is single-conductor building wire with cross-linked polyethylene (XLPE) insulation, made to be installed in conduit or other raceways. It's rated for wet and dry locations at up to 90°C and 600V.
Applications:
700 MCM aluminum XHHW-2 is installed in conduit and other NEC-recognized raceways for services, feeders, and branch circuits, in wet or dry locations at up to 600V. It's rated 375A at 75°C and 425A at 90°C. Typical uses:
-
350A feeders at full rating
-
700A services run as two parallel sets
-
1000A services run as three parallel sets
-
Transformer secondary conductors in commercial and industrial buildings
Also Known As:
700 xhhw-2 cable, 700 hxxw-2 cable, 700 rw90 cable, 700 rw90 wire, 700 type se cable style u type xhhw-2, 700 xhhw-2, 700 southwire xhhw-2, 700 xhhw-2 insulation.
700 MCM XHHW-2 Aluminum Data Center Applications
In data centers, 700 MCM aluminum XHHW-2 is used for long service and generator feeders, where its lower cost and weight add up across paralleled sets. Data center loads run continuously, so NEC 215.2 sizes feeders at 125% of the load unless the breaker is 100% rated. Terminations must be rated for aluminum.
-
Three parallel sets for 1000A service feeders
-
Two parallel sets for 700A distribution feeders
-
Long feeders from outdoor generators to paralleling switchgear
Standards:
-
XHHW-2 meet or exceed the following standards:
-
UL standard 44
-
Requirements of the National Electrical Code
-
ASTM standards B 800, B 801
-
Federal Specification J–C-30B
-
Sunlight resistant
Construction
Conductors:
Compact bare AA-8000 series aluminum alloy, Class B stranded per ASTM
Insulation:
XHHW-2 has abrasion, heat, and moisture resistant cross-linked polyethylene insulation. Cross linking a polyethylene helps to achieve an excellent strength that makes the material suitable for covering this cable used in harsh conditions.
Specifications:
-
Size AWG: 700 MCM
-
Stranding: 58
-
Conductor Diameter Inches: 0.877
-
Insulation Thickness Inches: 0.080
-
O.D. Inches: 1.037
-
New Weight lb/1000FT: 765 lbs
-
Ampacity at 75°C: 375 Amps
-
Ampacity at 90°C: 425 Amps
|
Compatible with Manufacturer |
|
| Houston item : |
Black : HW002A70001 Black : 700-01XHHWBLACKAL |
| Priority Wire & Cable : | Black : 700-01XHHW-2-ALUM |
| Southwire : |
Black : 27840899 Orange : 57634299 Yellow : 57634399 Brown : 57634199 Gray : 57634499 |
FAQ's
What is 700 MCM aluminum XHHW-2 used for?
What are the main differences between XHHW and XHHW-2 wires?
What is the difference between THHN and XHHW-2 wire?
Can XHHW-2 wire be buried underground?
Does XHHW-2 wire have to be run in conduit?
Is XHHW-2 wire sunlight resistant?
Can XHHW-2 wire be used in cold weather?
Is 700 MCM aluminum XHHW-2 used in data centers?
Call Us: 1-516-482-6313 Text Us: 1-516-703-3460
Garrie AI: Your Cable Guide