1000 MCM XHHW-2 Aluminum Cable 600V
Where are we? 4 Continents 9 Countries

Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Quick Support
1000 MCM XHHW-2 Aluminum Cable 600V
Allowable Ampacity for 1000 MCM XHHW-2 Aluminum Cable 600V at 75°C: 445 Amps
Allowable Ampacity for 1000 MCM XHHW-2 Aluminum Cable 600V at 90°C: 500 Amps
Applications:
Type XHHW-2/RW90 wires are primarily used in conduit or recognized raceways for services, feeders, and branch circuit wiring as specified in the National Electrical Code or the Canadian Electrical Code. XHHW-2/RW90 conductors may be used in wet or dry locations at temperatures not to exceed 90oC. Voltage rating for XHHW-2 conductors is 600 or 1000 volts, or 600 volts for RW90. Cable tray rated for 1/0 AWG and larger available upon request.
The particular applications of 1 000 kcmil wire are:
- Service entrance
- Main feeder circuits
- Major industrial equipment
- Conduit systems
- Busbars and power distribution systems
- Massive renewable energy installations
- Backup generators
Also Known As:
1000 xhhw-2 cable, 1000 hxxw-2 cable, 1000 rw90 cable, 1000 rw90 wire, 1000 type se cable style u type xhhw-2, 1000 xhhw-2, 1000 southwire xhhw-2, 1000 xhhw-2 insulation, 1000 kcmil aluminum wire, 1 000 kcmil wire, 1000 mcm aluminum wire, xhhw-2, 2 general cable
Standards:
- XHHW-2 meet or exceed the following standards:
- UL standard 44
- Requirements of the National Electrical Code
- ASTM standards B 800, B 801
- Federal Specification J–C-30B
- Sunlight resistant
Construction
Conductors:
XHHW-2 conductor is a soft drawn bare 8000 series aluminum, with Class B stranding per ASTM. Stranded conductors reduce power loss and are also easier to use in applications where flexibility is vital.
Insulation:
XHHW-2 has abrasion, heat, and moisture resistant cross-linked polyethylene insulation. Cross linking a polyethylene helps to achieve an excellent strength that makes the material suitable for covering this cable used in harsh conditions.
Specifications:
- Size AWG: 1000 MCM
- Stranding: 58
- Conductor Diameter Inches: 1.060
- Insulation Thickness Inches: 0.080
- O.D. Inches: 1.220
- New Weight lb/1000FT: 1067 lbs
- Ampacity at 75°C: 445 Amps
- Ampacity at 90°C: 500 Amps
|
Compatible with Manufacturer |
|
| Houston item : |
Black : HW002A10001 Black : 1000-01XHHWBLACKAL |
| Priority Wire & Cable : | Black : 1000-01XHHW-2-ALUM |
| Southwire : |
Black : 27842404 Orange : 66232199 Yellow : 66218699 Brown : 66218799 Gray : 66254199 |
Call Us: 1-516-482-6313 Text Us: 1-516-703-3460