350 MCM XHHW-2 Stranded Copper Building Wire
Where are we? 4 Continents 9 Countries

Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Quick Support
350 MCM XHHW-2 Stranded Copper Building Wire
Applications:
350 MCM copper XHHW-2 is installed in conduit and other NEC-recognized raceways for services, feeders, and branch circuits, in wet or dry locations at up to 600V. It's rated 310A at 75°C and 350A at 90°C. Typical uses:
-
300A feeders at full rating
-
350A home services under NEC 310.12
-
600A services run as two parallel sets
-
1200A services run as four parallel sets
350 MCM XHHW-2 Copper Data Center Applications
In data centers, 350 MCM copper XHHW-2 is used for feeders between switchgear, UPS systems, PDUs, and panels. Data center loads run continuously, so NEC 215.2 sizes feeders at 125% of the load unless the breaker is 100% rated.
-
Two parallel sets for 400 kVA UPS input and output (481A full load, 601A at 125%)
-
Four parallel sets for 1200A switchboards
-
Generator feeders to automatic transfer switches
Also Known As:
350 MCM Wire, 350 KCMIL Wire, 350 XHHW Cable 37 Strand, 350 KCMIL CU Cable, 350 MCM Copper Cable, 350 KCMIL CU Cable, 350 XHHW-2 Copper Building Wire, 350 XHHW Cable, 350 XHHW Service Wire, 350 XHHW-2 Copper Wire, 350 CU Building Wire, 350 Black Stranded CU SIMpull XHHW-2 Wire, Southwire 11306899, Southwire Wire, 350 MCM XHHW Building Wire, XHHW Stranded Building Wire.
Construction:
Conductor:
Class B compressed stranded bare copper per ASTM B3 and ASTM B8
Insulation:
Cross Linked Polyethylene (XLPE) with SIMpull Technology. Silicone-Free, Abrasion, High-Heat, Moisture Resistant.
Features:
- SIS- 8 AWG
- Sunlight resistant
- -40°C Cold bend
- FT1
- Gasoline and Oil Resistant II
- CT Rated- 1/0 AWG and larger
- FT4- 350 kcmil and larger
- RoHS/REACH Compliant
Standards:
- ASTM B3 Soft or Annealed Copper Wire
- ASTM B8 Concentric-Lay-Stranded Copper Conductors
- ASTM B787 19 Wire Combination Unilay-Stranded Copper Conductors
- UL 44 Thermoset-Insulated Wires and Cables
- UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
- CSA C22.2 No. 38 Thermoset-insulated wires and cables
- ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
- IEEE 1202/FT4 Flame Test (70,000 BTU/hr) 350kcmil and Larger
- Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
- Federal Specification A-A-59544
- NMX-J-451-ANCE Thermoset insulated wires and cables
- NOM-063-SCFI Electrical Products – Conductors – Safety Requirements
Specifications:
- Size : 350 MCM
- Number of Strands: 37
- Diameter Over Conductor ( Inch ): 0.661
- Insulation Thickness (mils): 65
-
Aprox. OD (inches): 0.803
-
Copper Weight ( lbs/mft ): 1080 lbs
- Net Weight ( lbs/mft ): 1158 lbs
- Min Bending Radius: 3.2 inch
- Max Pull Tension: 2800 lbs
- Allowable Ampacity At 60°C: 260 Amp
- Allowable Ampacity At 75°C: 310 Amp
- Allowable Ampacity At 90°C: 350 Amp
-
Southwire Part ( SimPull): 11306899
|
Compatible with Manufacturer |
|
|
Advanced Digital : |
20300CT |
|
Omni Cable : |
Black : M7300ST-01 |
|
Southwire : |
Black : 11306899 |
|
HWC : |
HW00235001 |
|
Service Wire Co : |
XH300BK |
FAQ's
What is 350 MCM copper XHHW-2 used for?
What are the main differences between XHHW and XHHW-2 wires?
What is the difference between THHN and XHHW-2 wire?
Can XHHW-2 wire be buried underground?
Does XHHW-2 wire have to be run in conduit?
Is XHHW-2 wire sunlight resistant?
Can XHHW-2 wire be used in cold weather?
Is 350 MCM copper XHHW-2 used in data centers?
Call Us: 1-516-482-6313 Text Us: 1-516-703-3460
Garrie AI: Your Cable Guide