As always, Nassau does a great job and gets me my wire fast. The wire is exactly what I wanted and the right lengths. They were out of one of the colors that I needed so they contacted me to see what I wanted to do. I told them just send me a different color which they did. Prices are good and the services great.
Where are we? 4 Continents 9 Countries
Got any Questions?
Speak with a real person who will go out of their way to help you!
10 AWG solid copper XHHW-2 is installed in conduit and other NEC-recognized raceways for services, feeders, and branch circuits, in wet or dry locations at up to 600V. It's rated 35A at 75°C and 40A at 90°C. NEC 240.4(D) limits 10 AWG copper to a 30A breaker, so that's the circuit size it's used for. Typical uses:
30A circuits for water heaters and dryers with screw terminals
30A circuits for small A/C condensers and equipment disconnects
Long 20A receptacle runs upsized to 10 AWG to limit voltage drop
Branch circuits in damp and wet locations run in conduit
Also Known As:
10 XHHW-2 RW90 Copper Building Wire, 10 XHHW-2 Cable, 10 XHHW-2 Service Wire, southwire 13724002, 10 XHHW-2 Copper Wire, XHHW-2 wire, 10 AWG XHHW Solid Building Wire, 10 Solid CU Wire, 10 solid wire copper.
Standards:
ASTM B3 Soft or Annealed Copper Wire
ASTM B8 Concentric-Lay-Stranded Copper Conductors
UL 44 Thermoset-Insulated Wires and Cables
ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
Federal Specification A-A-59544
NMX-J-451-ANCE Thermoset insulated wires and cables
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color
Recently Viewed Products
Download PDF Spec Sheet
FAQ's
What is 10 AWG solid copper XHHW-2 used for?
XHHW-2 is single-conductor building wire with cross-linked polyethylene (XLPE) insulation, which is where the "X" in its name comes from. "HHW" stands for high heat and water resistance, and "-2" means it's rated 90°C in wet locations as well as dry. 10 AWG solid copper XHHW-2 is installed in conduit or other NEC-recognized raceways at up to 600V and is rated 35A at 75°C. It's used for 30A circuits for water heaters, dryers, and small A/C units with screw terminals, and long 20A receptacle runs upsized to limit voltage drop.
What are the main differences between XHHW and XHHW-2 wires?
Both use cross-linked polyethylene (XLPE) insulation and are rated 600V. The difference is the wet rating. XHHW is rated 90°C in dry locations but only 75°C in wet locations. XHHW-2 is rated 90°C in both, and it passes stricter UL 44 moisture testing. XHHW-2 can be used anywhere XHHW is allowed.
What is the difference between THHN and XHHW-2 wire?
Both THHN/THWN-2 and XHHW-2 are 600V building wires rated 90°C in wet and dry locations, so the real difference is the insulation. THHN/THWN-2 has thin PVC insulation with a nylon jacket. XHHW-2 has a single, thicker layer of cross-linked polyethylene (XLPE), a thermoset material that doesn't melt. XHHW-2 holds up better to abrasion, moisture, and cold. THHN/THWN-2 has a smaller diameter, so more conductors fit in the same conduit, and it usually costs less.
Should I choose solid or stranded 10 AWG XHHW-2?
Both carry the same ampacity: 35A at 75°C, limited to a 30A breaker by NEC 240.4(D). Solid 10 AWG terminates more easily under receptacle and switch screws and holds its shape in boxes, so it's common for receptacle and lighting circuits in EMT. Stranded 10 AWG is more flexible, pulls more easily through long runs with several bends, and handles vibration better, so it's the usual choice for long pulls, flexible conduit, equipment connections, and data center rack whips.
How many 10 AWG XHHW-2 wires fit in 3/4" conduit?
Up to 8 conductors of 10 AWG XHHW-2 fit in 3/4" EMT or 3/4" Schedule 40 PVC under NEC Chapter 9 fill rules. In 3/4" Schedule 80 PVC, the limit is 6.
Can XHHW-2 wire be buried underground?
Not directly. XHHW-2 is not rated for direct burial, so it can't go in a trench without conduit. It can be installed underground inside conduit, because underground raceways are wet locations and XHHW-2 is rated 90°C wet. For burial without conduit, use a direct burial cable such as USE-2 or URD.
Does XHHW-2 wire have to be run in conduit?
Yes, in standard building installations. XHHW-2 is a single-conductor building wire meant for conduit or other recognized raceways. It can't be run exposed outdoors or fished through walls like NM cable, so inside a wall it has to be in conduit, such as EMT or flexible metal conduit. The NEC allows a few exceptions, such as cable tray for 1/0 AWG and larger conductors with a CT marking, or open wiring on insulators, but these are uncommon.
Is XHHW-2 wire sunlight resistant?
Yes. NNC's XHHW-2 is marked sunlight resistant, so it holds up in conduit runs exposed to the sun and where the wire leaves the conduit, such as at a weatherhead. Sunlight resistance doesn't replace the conduit requirement.
Can XHHW-2 wire be used in cold weather?
Yes. XLPE insulation stays flexible in the cold much better than PVC-insulated THHN, which makes XHHW-2 easier to pull in winter. It's commonly rated for installation down to -40°C (-40°F). Check the spec sheet for the exact minimum.
Can XHHW-2 be used as PV wire?
Yes, for the parts of a solar system that run in conduit. XHHW-2 is widely used in PV installations for DC home runs from the array to the inverter and for AC circuits from the inverter to the panel, as long as the system voltage stays within its 600V rating. It doesn't replace PV wire in exposed array wiring between modules, where NEC 690.31 calls for PV wire or USE-2.
As always, Nassau does a great job and gets me my wire fast. The wire is exactly what I wanted and the right lengths. They were out of one of the colors that I needed so they contacted me to see what I wanted to do. I told them just send me a different color which they did. Prices are good and the services great.