1000 MCM XHHW-2 Stranded Copper Building Wire

750 MCM XHHW-2 COPPER BUILDING WIRE
Roll over image to Zoom
1000 MCM XHHW-2 Stranded Copper Building Wire
Roll over image to Zoom
1000 MCM XHHW-2 Stranded Copper Building Wire
Roll over image to Zoom
1000 MCM XHHW-2 Stranded Copper Building Wire
Roll over image to Zoom
1000 MCM XHHW-2 Stranded Copper Building Wire
Roll over image to Zoom
1000 MCM XHHW-2 Stranded Copper Building Wire
Roll over image to Zoom
1000 MCM XHHW-2 Stranded Copper Building Wire
Roll over image to Zoom
1000 MCM XHHW-2 Stranded Copper Building Wire
Roll over image to Zoom
1000 MCM XHHW-2 Stranded Copper Building Wire
Roll over image to Zoom
1000 MCM XHHW-2 Stranded Copper Building Wire
SKU: NNC2516X
xhhw-2-copper-building-wire-conductor

Availability: In stock

Price:
Regular price
$62.29 /FT
Sale price
$62.29 /FT
Shipping Cost Calculated at Checkout. Standard Lead Time is 1 to 6 Business Days.
Free Shipping: On orders above $1000
Quantity must be 1 or more

Enter the required footage in the quantity box - Cut to one length

Customer Reviews

Be the first to write a review
0%
(0)
0%
(0)
0%
(0)
0%
(0)
0%
(0)

Where are we? 4 Continents 9 Countries

map
garrie

Got any Questions?

Speak with a real person who will go out of their way to help you!

Call Us: 1-516-482-6313Text Us: 1-516-703-3460

Product Information
Specification

1000 MCM XHHW-2 Stranded Copper Building Wire

Allowable Ampacity (Per NEC Table 310.16):

  • 60°C: 455 Amps
  • 75°C: 545 Amps
  • 90°C (XHHW-2 Rating): 615 Amps

Description:

1000 MCM XHHW-2 Copper Building Wire is a stranded conductor with cross-linked polyethylene (XLPE) insulation, designed for use in conduit, raceways, and feeders where high ampacity and durability are required. Rated for 600V, it operates in wet, dry, and corrosive environments, with a maximum temperature rating of 90°C.

Also Known As:

1000 XHHW-2 Copper Building Wire, 1000 XHHW Cable, 1000 XHHW Service Wire, 1000 XHHW Copper Wire, 1000 MCM XHHW Wire, 1000 MCM Copper XHHW-2 Cable, 1000 MCM Electrical Wire, 1000 MCM Stranded Copper XHHW-2.

Applications:

  • 500A feeders in a single run
  • 1000A services run as two parallel sets
  • 1600A services run as three parallel sets
  • Transformer secondaries and switchgear in industrial plants
  • Primary and secondary feeders in large commercial and industrial buildings
  • Underground conduit installations where moisture resistance is required
  • Main service conductors for high-load electrical panels
  • Backup generator wiring for hospitals, data centers, and critical facilities
  • Cable tray wiring in industrial settings requiring high ampacity

1000 MCM XHHW-2 Copper Data Center Applications

In data centers, 1000 MCM copper XHHW-2 is used for feeders between switchgear, UPS systems, PDUs, and panels. Data center loads run continuously, so NEC 215.2 sizes feeders at 125% of the load unless the breaker is 100% rated.

  • Two parallel sets for 1000A feeders

  • Three parallel sets for 1000 kVA UPS systems (1203A full load, 1504A at 125%)

  • Four parallel sets for 2000A switchboards, with fewer conductors per phase than smaller sizes in tight electrical rooms

Construction:

Conductor:

  • Material: Annealed bare copper (concentrically stranded)
  • Properties: High conductivity, moisture resistance, and excellent durability

Insulation:

  • Material: Cross-linked polyethylene (XLPE)
  • Properties: Flame-retardant, resistant to chemicals, moisture, and abrasion

Standards & Compliance:

  • UL Standard 44 – Thermoset-Insulated Wires and Cables
  • ASTM B3 & B8 – Soft and Concentric-Lay-Stranded Copper Conductors
  • Federal Specification A-A-59544
  • RoHS/REACH Compliant
  • NEC Article 310.16 – Ampacity Ratings
  • ICEA S-95-658 (NEMA WC70) – Power Cables Rated 2000V or Less

Specifications:

  • Size: 1000 MCM
    Number of Strands: 61
    Diameter Over Conductor (Inches): 1.117
    Insulation Thickness (mils): 80
    Weight per 1,000 ft: 3240 lbs
    Insulation: XLPE

Compatible with Manufacturer

Southwire :

Black : 11313499
White : 13862498
Red : 13862398
Blue : 13862298
Green : 66844999

Yellow : 67846499
Orange : 67846599
Brown : 67846399

HWC : 

HW00210001

Service Wire Co : 

XH600BK


*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color
Download PDF Spec Sheet

FAQ's

What is 1000 MCM copper XHHW-2 used for?

XHHW-2 is single-conductor building wire with cross-linked polyethylene (XLPE) insulation, which is where the "X" in its name comes from. "HHW" stands for high heat and water resistance, and "-2" means it's rated 90°C in wet locations as well as dry. 1000 MCM copper XHHW-2 is installed in conduit or other NEC-recognized raceways at up to 600V and is rated 545A at 75°C. It's used for 500A feeders, 1000A and 1600A services in parallel sets, and transformer secondaries in industrial plants.

What are the main differences between XHHW and XHHW-2 wires?

Both use cross-linked polyethylene (XLPE) insulation and are rated 600V. The difference is the wet rating. XHHW is rated 90°C in dry locations but only 75°C in wet locations. XHHW-2 is rated 90°C in both, and it passes stricter UL 44 moisture testing. XHHW-2 can be used anywhere XHHW is allowed.

What is the difference between THHN and XHHW-2 wire?

Both THHN/THWN-2 and XHHW-2 are 600V building wires rated 90°C in wet and dry locations, so the real difference is the insulation. THHN/THWN-2 has thin PVC insulation with a nylon jacket. XHHW-2 has a single, thicker layer of cross-linked polyethylene (XLPE), a thermoset material that doesn't melt. XHHW-2 holds up better to abrasion, moisture, and cold. THHN/THWN-2 has a smaller diameter, so more conductors fit in the same conduit, and it usually costs less.

Can XHHW-2 wire be buried underground?

Not directly. XHHW-2 is not rated for direct burial, so it can't go in a trench without conduit. It can be installed underground inside conduit, because underground raceways are wet locations and XHHW-2 is rated 90°C wet. For burial without conduit, use a direct burial cable such as USE-2 or URD.

Does XHHW-2 wire have to be run in conduit?

Yes, in standard building installations. XHHW-2 is a single-conductor building wire meant for conduit or other recognized raceways. It can't be run exposed outdoors or fished through walls like NM cable, so inside a wall it has to be in conduit, such as EMT or flexible metal conduit. The NEC allows a few exceptions, such as cable tray for 1/0 AWG and larger conductors with a CT marking, or open wiring on insulators, but these are uncommon.

Is XHHW-2 wire sunlight resistant?

Yes. NNC's XHHW-2 is marked sunlight resistant, so it holds up in conduit runs exposed to the sun and where the wire leaves the conduit, such as at a weatherhead. Sunlight resistance doesn't replace the conduit requirement.

Can XHHW-2 wire be used in cold weather?

Yes. XLPE insulation stays flexible in the cold much better than PVC-insulated THHN, which makes XHHW-2 easier to pull in winter. It's commonly rated for installation down to -40°C (-40°F). Check the spec sheet for the exact minimum.

Is 1000 MCM copper XHHW-2 used in data centers?

Yes. 1000 MCM copper XHHW-2 runs in three parallel sets for a 1000 kVA, 480V UPS (1504A at 125%) and in four sets for 2000A switchboards, with fewer conductors per phase in tight electrical rooms.