18 AWG 6P Individual and Overall Shield Instrumentation Tray Cable VNTC TC-ER 600V
Application:
• TC-ER SPOS Instrumentation Cables are suitable for control,instrumentation and process control circuits, where protection against electrostatic interference from both outside of the cable and from pair to pair is needed. The cables are suitable for wet or dry applications, direct burial, indoor or outdoor locations,installed in cable trays, ducts, aerially or conduits and for applications up to 600 volt and temperatures up to 90°C. TC-ER SPOS Instrumentation Cables are suitable for use in Class 1 Division 2 Hazardous locations per NEC
Scope:
• This Instrumentation Cables is UL listed under Article 340 of the NEC and is suitable for cable tray use in Class 1, Division 2 hazardous locations. The cable can be used in wet or dry locations and up to conductor temperatures of 90°C. The addition of nylon over the conductors provides excellent oil and gasoline protection.
• The individually shielded pairs and triads are completely isolated from each other by use of a polyester tape. This isolation assures maximum protection from crosstalk and common mode interference. An overall shield provides additional protection.
• The flame properties meet or exceed the requirements of both the UL 70,000 BTU vertical tray flame test and the comparable IEEE-383 flame test. A 210,000 BTU rating is also available upon request.
Also Known As:
18 AWG 6P Shielded VNTC Cable, 18 AWG 6P Instrumentation Cable, 18 AWG 6P 600V VNTC Control Cable, 600V Shielded Instrumentation Tray Cable, 18 AWG 6P TC-ER Instrument Cable, VNTC Tray Cable, 18/6P 600V Shielded Control Cable.
Construction:
Class B, stranded per ASTM B-3 and ASTM B-8.
Conductors are type TFN listed under UL 62.
Available in tinned copper upon request.
Primary Insulation:
105°C rated PVC and nylon jacket
Shielding:
Aluminum polyester foil with 100% coverage on each pair,
with an overall aluminum polyester foil with 100% coverage
with a tinned copper drain wire in contact with all shields
Jacket:
Polyvinyl Chloride (PVC) jacket, which is water, chemical,
sunlight and abrasion resistant
Specifications:
• AWG: 18
• No. of Pairs: 6
• Nominal Jacket Thickness (In): .047
• Nominal Outside Diameter (In): .498
• Pulling Tension (Pounds): 149
• Nominal Weight 1000 FT (Pounds): 139