Applications
X-Olene FMR low voltage power and control cables are recommended for use in power generating plants, combined cycle power units, co-generation plants and in substations; designed especially for critical circuits where continuity of service is of prime importance. These cables are TC-ER listed and meet UL requirements. As TC-ER cable, they are permitted for use on power, lighting, control, and signal circuits; indoors or outdoors; in cable trays, raceways, direct burial in the ground, or where supported in outdoor locations by a messenger; for Class 1 circuits as permitted by Article 725 of the NEC; and in cable trays in Class I Division 2 hazardous locations in industrial establishments where the conditions of maintenance and supervision assure that only qualified persons will service the installation.
Cables marked TC-ER may also be used between a cable tray and the utilization equipment or device, when installed in accordance with NEC 336.10(7).
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
Insulation X-Olene FMR is Okonite’s trade name for its heat, moisture, and flame resistant, crosslinked polyethylene insulating compound.
Overall Jacket Okolon-TP-CPE is a thermoplastic chlorinated polyethylene compound. This jacket has excellent resistance to moisture, ozone, oil and many chemicals.
Specifications Conductors: Uncoated soft copper per ASTM B-3. Sizes smaller than #8 are compress stranded per ASTM B-8. Sizes #8 and larger are compact stranded per ASTM B-496. Insulation: Okoseal insulation with nylon covering per UL 1581. Color Coding: Base colors and tracers as shown on reverse of Data Sheet. Grounding Conductor(s): Where indicated, bare stranded copper per ASTM B-8 for sizes #7 AWG and smaller, compact round for sizes #8 AWG and larger per ASTM B-496 and in accordance with NEC Table 250.122. Assembly: Conductors cabled in accordance with UL 1277 and 1309 using fillers, as necessary, with a cable tape overall. Overall Jacket: Complies with UL 1277. The Okolon-TP-CPE compound meets or exceeds the requirements of UL 1581, ICEA S-73-532 (NEMA WC57) & ICEA S-95-658 (NEMA WC70). UL Listed as Type TC-ER cable with a sunlight resistant jacket and for direct burial. Sizes 4 AWG and larger, without a grounding conductor, are Type TC only (not ER).
Product Features
Complies with UL 1277. The OkolFor cable tray use.
For direct burial.
Sunlight resistant.
Insulated conductors are UL rated XHHW-2 and VW-1.
Flame Retardant - passes the vertical tray flame test requirements of IEEE 383-1974 & 1202-1991 and UL 1277 and ICEA T-29-520 (210,000 BTU/hr.).
UL listed for cable tray use.
90°C continuous rating in wet or dry locations 130°C emergency overload rating 250°C short circuit rating.
X-Olene FMR Okolon-TP-CPE Type TC-ER cables are quality control inspected to meet or exceed applicable industry standards.
Resistant to moisture and most chemical atmospheres.
Thermal stability at elevated temperatures.
Easy to install and terminate.
Mechanically rugged.
High dielectric strength.
Small diameter, lightweight.
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.