Select your reel lengths by filling out the fields below. You may have up to 5 different cuts per order.
X =
TOTAL
=
REEL CUT PRICE
=
Product Information
Specification
About:
NHXCH-FE cable is specifically engineered to maintain circuit integrity under fire conditions, ensuring power and communication lines remain operational in emergency situations. Its design caters to installations where safety and performance are critical, particularly in fire scenarios.
Also Known As:
•NHXCH: This part of the name typically indicates the cable's halogen-free and fire-resistant characteristics. "NH" usually signifies halogen-free material, and "XCH" might relate to the cable's fire-resistant properties. •FE: Often stands for "Fire Resistant" or "Functional Integrity," denoting the cable's ability to function in extreme conditions, particularly fire.
Application:
• Emergency Circuits: Ensuring the functionality of critical circuits during fires, such as emergency lighting, alarm systems, and smoke extraction units. •Safety Systems: Used in fire alarm systems, emergency exit lightings, and other safety installations requiring operation during fire incidents. • Infrastructure Resilience: Ideal for buildings, tunnels, and public infrastructures where maintaining circuit integrity during fire is vital.
Standards:
•IEC 60331: Pertains to the cables' ability to withstand fire and maintain circuit integrity. •EN 50200: Defines the performance requirements for maintaining circuit integrity under fire conditions. •BS 6387: Specifies testing methods for cables required to maintain circuit integrity under various conditions like fire, water, and mechanical stresses.
Construction:
• Conductor: Solid or stranded red copper conductor Cl. 1 or 2, acc. to IEC 60228, DIN VDE 0259 •Insulation: Special core insulation of mica tape and cross-linked polymer type HI1, acc.to DIN VDE 0207 part 23 •Colour cores: acc. to DIN VDE 0293-308, HD 308 S2 •Stranding: Cores stranded in layers •Wrapping: Glass-fibre •Screen: Red copper wires and one or two copper tape(s) applied helically • Outer Sheath: orange (RAL 2003), polymer compound acc. to DIN VDE 0207 part 24, flame retardant orange (RAL 2003), polymer compound acc. to DIN VDE 0207 part 24, flame retardant
Features:
• Security cable, 0,6/1 kV, with improved fire characteristics • Insulation integrity under flame propagation to VDE 0472 part 814 IEC 60331 • Burning behavior in fire(funtionality) of the complete cable system to DIN 4102 part 12 (30 min.) • FE 180: insulation integrity for 180 min. Test to DIN VDE 0472 part.814 IEC 60331 • E 30:functionally for 30 min.Test to DIN 4102 part.12 • re: circular solid conductor • rm: circular stranded conductor • sm: sector-shaped stranded conductor • se: sector-shaped solid conductor
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.