750 MCM 3C Type MV -105 Copper 5/8kV NLEPR Insulation 133/100% IL ARMOR-X Yellow PVC Jacket
Where are we? 4 Continents 9 Countries

Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Quick Support
750 MCM 3C Type MV -105 Copper 5/8kV NLEPR Insulation 133/100% IL ARMOR-X Yellow PVC Jacket
Application:
The 5KV ARMOR-X MC HL are armored cables for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Suitable for VFD application. Rated for 1000 lbs./FT maximum sidewall pressure Type MV-105 Three Conductor Copper, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, Continuous Corrugated Welded Aluminum Armor - ARMOR-X, Polyvinyl Chloride (PVC) Jacket. Suitable for VFD Applications. Type MC HL. Silicone Free
Also known as:
750 MCM 3C MV-105 Three-Conductor Copper Cable 5/8 kV Three Conductor Cable with NLEPR Insulation 750 MCM 3C Medium Voltage Three-Conductor Copper Cable with Armor-X Protection 133/100% Insulation, Three-Conductor Copper Cable with Yellow PVC Jacket 5/8 kV NLEPR Insulated Copper Cable with Armor-X, Yellow PVC Jacket 750 MCM 3C Medium Voltage Copper Cable with IL Armor-X and Yellow PVC Jacket
Construction:
Conductor:
Class B compressed stranded bare copper per ASTM B3 and B8 (Tinned Copper per ASTM B33 optional)
Conductor Shield:
Semi-conducting cross-linked copolymer
Insulation:
115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level
Insulation Shield:
Strippable semi-conducting cross-linked copolymer
Copper Tape Shield:
Helically wrapped 5 mil copper tape with 25% overlap
Grounding Conductor:
3 Class B compressed stranded bare copper ground per ASTM B3 and B8 (Tinned Copper per ASTM B33 optional)
Filler:
Wax paper filler
Binder:
Polypropylene tape
Armor:
ARMOR-X Continuous Corrugated Welded Aluminum Armor
Overall Jacket:
Polyvinyl Chloride (PVC)
Standards:
• ASTM B3 Soft or Annealed Copper Wire
• ASTM B8 Concentric-Lay-Stranded Copper Conductors
• ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
• UL 1072 Medium-Voltage Power Cables
• UL 1569 Metal-Clad Cables
• UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
Specification:
• Size: 750 MCM
• Number of Conductor: 3 + 3G
• Number of Strands: 61
• Diameter Over Conductor (inch): 0.968
• Diameter Over Insulation (inch): 1.254
• Diameter Over Insulation Shield: 1.314
• Ground No. x AWG: 3x4
• Diameter Over Armor (inch): 3.540
• Jacket Thickness (mil): 85
• Approx. OD (In): 3.710
• Copper Weight lb/1000ft: 7723
• Approx. Weight (Lbs/1000'Ft): 10969
• DC Resistance @ 25°C Ω /1000ft: 0.014
• AC Resistance @ 90°Ω /1000ft: 0.023
• Allowable Ampacity In Duct 90/105°C Amp : 530/570
• Allowable Ampacity In Air 90/105°C Amp: 615/685
|