750 MCM 3C HVTECK Copper 175 mil TRXLPE TS AIA 15kV 100% IL Red PVC Jacket CSA

Where are we? 4 Continents 9 Countries


Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Quick Support
750 MCM 3C HVTECK Copper 175 mil TRXLPE TS AIA 15kV 100% IL Red PVC Jacket CSA
Application:
The 15kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Also Known As:
750 MCM 3C HVTECK 15kV 3 conductor copper cable, 3/C 175 mil TRXLPE shielded cable, Copper medium voltage power cable 15kV, 750 MCM 3C AIA armored HVTECK 15kV cable, CSA approved 15kV copper cable, Red PVC jacket TRXLPE cable 15kV, 100% insulation level HVTECK cable, TS armored 15kV copper conductor, 750 MCM 3C HVTECK 15kV underground power cable, Copper 3 conductor armored TRXLPE cable.
Construction:
• Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
• Conductor Shield: Semi-conducting cross-linked copolymer
• Insulation: 175 Mils Tree Retardant Cross Linked Polyethylene 100% insulation level
• Insulation Shield: Strippable semi-conducting cross-linked copolymer
• Copper Tape Shield: Helically wrapped 5 mil copper tape with 25% overlap
• Filler: Interstices filled with non-hydroscoping/non-wicking fillers
• Grounding Conductor: Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
• Binder: Polypropylene tape
• Inner Jacket: PVC inner jacket
• Armour: Aluminum Interlocked Armour (AIA)
• Overall Jacket: Red Polyvinyl Chloride (PVC) Jacket
Standards:
• ASTM B3 Soft or Annealed Copper Wire
• ASTM B8 Concentric-Lay-Stranded Copper Conductors
• CSA C22.2 No. 174 Cables in Hazardous Locations
• CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
• CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
• CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
• CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
• CSA HL - for Hazardous Locations rating
• CSA SUN RES - for Sunlight Resistant rating
• ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
• ICEA T-29-520 Flame Test (210,000 BTU/Hr)
• IEEE 383 Flame Test (70,000 btu)
• IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
• FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
• AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
Specifications:
• Size: 750 MCM
• Number of Strands: 61
• Diameter Over Conductor (inch): 0.968
• Diameter Over Insulation (inch): 1.374
• Insul. Thickness mil: 175
• Diameter Over Insulation Shield (inch): 1.434
• Ground Size AWG: 2
• Inner Jacket Thickness (mil): 125
• Diameter Over Armor (inch): 3.747
• Overall Jacket Thickness mil : 85
• Approx. OD inch : 3.917
• Copper Weight lb/1000ft: 7301
• Approx. Weight (Lbs/1000'Ft): 11465
• Min Bending Radius (In): 27.4
• DC Resistance @ 25°C Ω /1000ft: 0.014
• AC Resistance @ 90°Ω /1000ft: 0.020
• Inductive Reactance @ 60HzΩ/1000ft: 0.030
• Allowable Ampacity In Air 90°C Amp: 678
• Allowable Ampacity Directly Buried 90°C Amp: 668