6 AWG 2C Bare Copper Tape Unshielded PVC N1VC7V-K 0.6/1KV Industrial Low Voltage Cable

Where are we? 4 Continents 9 Countries


Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Quick Support
Allowable Ampacity for 6 AWG 2C Bare Copper Tape Unshielded PVC N1VC7V-K 0.6/1KV Industrial Low Voltage Cable: 100 Amps
About:
This cable is designed for low voltage power distribution. It is constructed with a bare copper conductor and PVC insulation, making it suitable for various industrial applications. Its rating of 0.6/1 KV indicates its suitability for low voltage systems.
Also Known As:
This cable might be referred to by different names depending on the manufacturer or region. It is commonly recognized as part of the Sumflex® RVFV-K series or as an electrical or flexible cable.
Application:
The cable is ideal for industrial connections, indoor and outdoor distribution, and other applications that require robust and reliable electrical wiring. It can be used in underground networks for low voltage distribution, outdoor lighting installations, and for internal electrical power distribution.
Standards:
It meets the criteria for the classification of construction products according to CPR Regulation 305/2011 and the EN 50575 standard. It also complies with relevant NEC articles for plenum-rated cables.
Construction:
• Conductor: Flexible red copper conductor Cl.5, acc.to IEC 60228
• Insulation: PVC type R2
• Colour cores: acc. to DIN VDE 0293-308, HD 308 S2 from 6 cores black cores with consecutive numbers acc. to EN 50334; green-yellow earth-wire from 3 core
• Wrapping: Not fibrous and hygroscopic materials
• Screen: Two alternated copper tapes
• Outer sheath: Light blue (RAL 5012), PVC type Rz
Features:
• EN 60332-1-2 CEI 20-22II comparable to IEC 60332-3-22
• According to CEI 20-14
• UNEL TABLES 35357 - 35376
• Indoor and outdoor use
Specifications:
• No. of cores x cross section n x mm²: 2x16
• AWG no.: 6
• Outer-Ø ca.mm ± 10%: 22,8
• Nominal voltage: Uo/U 0,6/1 kV
• Test voltage: 4 kV
• Min. bending radius: 8 x d
• Tensile stress: During installation: 50 N/mm², Static stress: 15 N/mm²
• Cable weight approx. kg/km: 820
• Part Number: 46100GB3020M62