2-2-2-2 Palomino Quadruplex Overhead Aluminum Conductor


our commitment
payments types accepted
See all »have any questions?
Product Information
Specification
2-2-2-2 Palomino Quadruplex Overhead Aluminum Conductor
Allowable Ampacity for 2-2-2-2 Palomino Quadruplex Overhead Aluminum Conductor XLP at 90°C: 135 Amps
Allowable Ampacity for 2-2-2-2 Palomino Quadruplex Overhead Aluminum Conductor Poly at 75°C: 105 Amps
Applications:
The electrical cable known as aluminum quadruplex overhead service drop cable supplies three phase power and is also referred to as the three phase cable. The quadruplex overhead wire is designed for service at 600 V or lower (phase to phase), at a maximum conductor temperature of 75°C.
The 3 phase power cable has four conductors, with three of them being live conductors and one being a messenger conductor. The three aluminum quadruplex cable conductors are made of soft aluminum and extruded cross-linked polyethylene insulation, which protects the wire from the harsh outdoor environmental conditions; the messenger of this electrical cable is left bare.
Also Known As:
2-2-2-2 palomino aluminum quadruplex, 2-2-2-2 palomino overhead service drop, 2-2-2-2 palomino three phase cable, 2-2-2-2 palomino 3 phase cable, 2-2-2-2 palomino 3 phase power cable, 2-2-2-2 palomino 3 phase extension cord, 2-2-2-2 palomino 3 phase aluminum cable, 2-2-2-2 palomino 3 phase electrical cable, 2-2-2-2 palomino three phase power cable, 2-2-2-2 palomino quadruplex wire, 2-2-2-2 palomino quadruplex overhead wire, 2-2-2-2 palomino overhead service entrance cable.
Standards:
-
ASTM B-230
-
ASTM B-231
-
ASTM B-232
-
ASTM B-399
-
ICEA S -76 - 474
Construction
Conductors:
Aluminum quadruplex overhead service drop cable has a concentric strand or compressed 1350-H19 series aluminum conductor.
Messenger:
Quadruplex overhead wire has a bare ACSR messenger. Optional constructions include a messenger of AAC or 6201 alloy.
Insulation:
Quadruplex overhead service entrance cable has a black cross linked polyethylene (XLP) insulation.
Specifications:
-
Size AWG: 2
-
Stranding: 7/w
-
Insulation Thickness (mils): 0.045
-
Neutral Size AWG: 2
-
Weight lbs./1000ft: XLP: 362
-
Weight lbs./1000ft: Poly: 342
-
Ampacity: XLP: 135
-
Ampacity: Poly: 105