2 AWG 1C Stranded Aluminium Shield Overall BC Tape Red PE ARG7H1E 12/20KV Medium Voltage Cable
Where are we? 4 Continents 8 Countries
Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Chat
Live Chat: Bottom Right Corner!
Email Us
info@nassaunationalcable.com
Quick Support
Product Information
Specification
2 AWG 1C Stranded Aluminium Shield Overall BC Tape Red PE ARG7H1E 12/20KV Medium Voltage Cable
Allowable Ampacity for 2 AWG 1C Stranded Aluminium Shield Overall BC Tape Red PE ARG7H1E 12/20KV Medium Voltage Cable:100 Amps
About:
ARG7H1E cable is typically used for medium voltage applications, transmitting electricity at voltages in a range that is higher than low voltage cables but lower than high voltage cables.
Also Known As:
• ARG7H1E cable
• Stranded Aluminium Shield cable
• Overall BC Tape cable
• Red PE Medium Voltage Cable
Application:
• Power transmission in industrial, infrastructure, and utility applications.
• Distribution networks, substations, and in settings where underground or overhead medium voltage power distribution is required.
• Suitable for environments that require a robust and durable cable design.
Standards:
• International standards such as IEC 60502-2.
• National standards relevant to where they are used (e.g., ANSI/ICEA for the USA).
• Industry-specific certifications ensuring they are fit for purpose in terms of electrical performance, safety, and durability.
Construction:
• Conductor: Stranded Plain Aluminium Conductor Cl.2, Acc. To Iec 60228
• Inner Semi-conductive Layer: Extruded Elastomeric Compound
• Insulation: Special Epr Type Dih2
• Outer Semi-conductive Layer: Extruded Elastomeric Compound
• Screen: Red Copper Wires And One Or Two Copper Tape(S) Applied Helically, If Necessary
• Outer Sheath: Red(Ral 3000), Pe Type Dmz1
Features:
According To Iec 60502-2
Specifications:
• AWG No: 2
• No.of cores x cross section n x mm2: 1 x 35
• Outer-Ø ca.mm ± 10%: 26,1
• Nominal voltage: Uo/U 12/20 kV, Uo/U 18/30 kV
• Test voltage: Uo/U 12/20 kV = 29 kV
Uo/U 18/30 kV = 45 kV
• Temperature range: - 25 oC up to + 105 oC
• Max short circuit temperature:+ 300 oC
• Min. bending radius: 13 x d
• Max. tensile stress: 60 N/mm2
• Cable weight approx. kg/km: 570
• Part Number: 48040URL010M63
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color
Download PDF Spec Sheet
Reviews
Call Us: 1-516-482-6313 Text Us: 1-516-703-3460