Application:
The 2.4KV ARMOR-X Type MC-HL are armored cables for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial or concrete encasement and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 130°C for emergency overload, 250°C for short circuit conditions, and -50°C for cold bend. For uses in Class I, II, and III, Division 1 and 2 hazardous locations per NEC Article 501, 502, and 503. Suitable for VFD application.
Also Known As:
2/0 AWG 3C MV-105 copper cable, Three conductor VFD cable, 2.4kV VFD cable, NLEPR insulation cable, ARMOR-X PVC jacket cable, 2/0 AWG 3C VFD cable copper conductor, MV-105 2.4kV cable, Yellow PVC jacket cable, 100% IL ARMOR-X cable, 2/0 AWG 3C VFD motor cable.
Standards:
• ASTM B3 Soft or Annealed Copper Wire
• ASTM B8 Concentric-Lay-Stranded Copper Conductors
• ASTM B33 Standard Specification for Tin-Coated Soft or Annealed Copper Wire
• UL 1072 Medium-Voltage Power Cables
• UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test (1/0 and Larger)
• ICEA S-96-659 (NEMA WC 71) 2001-5000 V Non shielded Cables
• IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test
• Made in America: Compliant with both Buy American and Buy America Act (BAA) requirements per 49 U.S.C. § 5323(j) and the Federal Transit Administration Buy America requirements per 49 C.F.R. part 661
Construction:
• Conductor: Class B compressed stranded bare copper per ASTM B3 and B8 (Tinned Copper per ASTM B33 optional)
• Conductor Shield: Semi-conducting cross-linked copolymer
• Insulation: 90 Mils Ethylene Propylene Rubber (EPR)
• Grounding Conductor: 3 Class B compressed stranded bare copper ground per ASTM B3 and B8 (Tinned Copper per ASTM B33 optional)
• Filler: Wax paper filler
• Binder: Polypropylene tape
• Armor: ARMOR-X Continuous Corrugated Welded Armor
• Overall Jacket: Polyvinyl Chloride (PVC)
Specifications:
• Size: 2/0 AWG
• Number of Conductor: 3 + 1G
• Number of Strands: 19
• Diameter Over Conductor (inch): 0.405
• Diameter Over Insulation (inch): 0.625
• Ground No. x AWG: 3 x 8
• Diameter Over Armor (inch): 1.670
• Jacket Thickness (mil): 70
• Approx. OD (In): 1.810
• Copper Weight lb/1000ft: 1399
• Approx. Weight (Lbs/1000'Ft): 2338
• Min Bending Radius (In): 12.6
• DC Resistance @ 25°C Ω /1000ft: 0.081
• AC Resistance @ 90°Ω /1000ft: 0.102
• Inductive Reactance @ 60HzΩ/1000ft: 0.032
• Allowable Ampacity In Duct 90/105°C Amp : 200/220
• Allowable Ampacity In Air 90/105°C Amp: 215/240