FEATURES:
• Reduces installation costs up to 50% over pipe and wire.
• Lightweight aluminum armor--as much as 45% lighter than steel MC Cable.
• UL Classified 1, 2, and 3 hour Through Penetration Firestop Systems: W-J-3037, W-L-3110, W-L-3113, W-L-3117,
W-L-3120, W-L-3121, W-L-3160, C-AJ-3115, C-AJ-3140, C-AJ-3142, C-AJ-3145, C-AJ-3173, C-AJ-3202, C-AJ-4065,
C-AJ-4066, F-C-3038.
• Cable reverse wound on reel for ease of pulling and installation. When pulling from coils, pull from inside to ensure ease
of installation.
• Anti-short bushings are not required for use with MC cable per the NEC and UL
CONSTRUCTION:
Armorlite Type MC Cable is constructed with soft-drawn copper, Type THHN/THWN conductors rated 90°C dry
available in sizes 14 AWG through 2 AWG, and a green insulated grounding conductor. The conductors are cabled together
and a binder tape bearing the print legend is wrapped around the assembly. Aluminum interlocking armor is applied over the
assembly.
APPLICATIONS:
• Branch, feeder and service power distribution in commercial, industrial, institutional, and multi-residential buildings.
• Power, lighting, control, and signal circuits.
• Fished or embedded in plaster.
• Concealed or exposed installations.
• Environmental air-handling spaces per NEC 300.22 (C).
• Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
• Installation in cable tray and approved raceways.
• Under raised floors for information technology equipment conductors and cables per NEC 645.5(D) & 645.5(D)(2).
• Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
STANDARDS & REFERENCES:
• UL 83
• UL 1569
• UL 1685
• Federal Specification A-A59544 (formerly J-C-30B)
• FT4/IEEE 1202 (70,000 Btu/hr) Vertical Cable Tray Flame Test
• NEC
• Listed for use in UL 1, 2 and 3 Hour Through Penetration Firestop Systems