112-09-1591 Okonite-FMR Type RHH or RHW-2,VW-1 - 750 MCM AWG - 61 Strands
Where are we? 4 Continents 8 Countries
Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Chat
Live Chat: Bottom Right Corner!
Email Us
info@nassaunationalcable.com
Quick Support
Insulation
Okonite-FMR is Okonite’s trade name for its heat resistant, mechanically rugged black pigmented ethylene-propylene base insulating compound.
Applications
Okonite-FMR Type RHH or RHW-2 600 Volt Power and Control Cables are recommended for general low voltage power and control applications. Okonite-FMR flame retardant insulated power cables may be used in generating plants, substations and industrial plants. Type RHH or RHW-2 may be used up to 90°C in dry or wet locations. These cables may be installed in wet or dry locations, indoors or outdoors, in raceways, underground ducts, cable tray (size 1/0 AWG and larger per NEC 392) or lashed to a messenger for aerial installation.
Specifications
Conductor:Uncoated soft copper per ASTM B-3. Solid per ASTM B-3. Sizes smaller than #8 are compress stranded per ASTM B-8. Sizes #8 and larger are compact stranded per ASTM B-496.
Insulation:Meets or exceeds all requirements of ICEA S-95-658, NEMA WC-70, IEEE Standard 383, and UL 44.
Listed by Underwriters Laboratories, Inc. as Type RHH or RHW-2, VW-1.
Product Features
- Sizes 1/0 AWG and larger pass the Vertical Tray Flame Test requirements of UL 1581 for use in cable tray.
- Passes the ICEA T-29-520 210,000 Btu/hr. vertical tray flame test (sizes 6 AWG and larger).
- Passes the IEEE 383 Vertical Tray Flame Test.
- Passes the IEEE 1202 Vertical Tray Flame Test. (sizes 1/0 AWG and larger).
- Extreme heat resistance 90°C continuous rating; 130°C emergency overload rating; 250°C short circuit rating.
- Rated 90°C wet or dry.
- Exceptional resistance to deformation at high temperatures.
- Stable electrical properties.
- Low SIC and power factor.
- Low moisture absorption.
- Mechanically rugged.
- Resistant to weather.
- Smaller diameter.
- More flexible, easier to install, terminate, or splice than XLPE insulation.
- Flame retardant.
- UL Listed, UL Rated VW-1.
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
Call Us: 1-516-482-6313 Text Us: 1-516-703-3460