1000 MCM Aluminum SW Standard Wall Laminate Sheath 230 kV XLPE Power Cable
Where are we? 4 Continents 9 Countries

Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Quick Support
1000 MCM Aluminum SW Standard Wall Laminate Sheath 230 kV XLPE Power Cable
Applications:
Predominantly used for underground transmission in conduit systems, suitable for use in wet or dry locations, direct burial, underground duct, and where exposed to sunlight. To be used at 230,000 volts or less and at conductor temperatures not to exceed 90°C for normal operation Segmental Cu smooth conductor shield, super clean XLPE insulation, true triple extrusion and dry cured, firmly bonded insulation shield, Cu moisture impervious sheath, PE jacket with extruded semi-conductive outer layer.
Also Known As:
1000 MCM 230 kV Aluminum Conductor XLPE Insulated Corrugated Sheath Power Cable 230 kV HV XLPE Aluminum Power Cable with Corrugated Metallic Sheath 230 kV Aluminum 1000 MCM XLPE Underground Transmission Cable 230 kV Single-Wire Aluminum XLPE High-Voltage Cable 230 kV Corrugated Aluminum Sheathed XLPE Power Cable 230 kV Extruded Dielectric 1000 MCM XLPE Transmission Cable 230 kV Aluminum Conductor High-Voltage Underground Cable 230 kV XLPE Insulated Metallic Corrugated Sheath Cable 230 kV Aluminum HV Power Transmission Cable 230 kV XLPE Corrugated Sheath Utility Power Cable 230 kV Aluminum Conductor Standard Wall XLPE Cable
Cable Construction:
• Concentric Stranded, Compact, or Segmental Alumimum Conductor
• Smooth Conductor Shield
• Super Clean XLPE Insulation
• True Triple Extrusion and Dry Cured
• Firmly Bonded Insulation Shield
• Aluminum Moisture Impervious Sheath
• Polyethylene Jacket with Extruded Semi-Conductive Outer Layer
CABLE DATA:
Voltage Characteristics (kV)
Max Voltage Rating: 245
BIL Rating: 1050
Temperatures (°C)
Nominal Conductor: 90
Max. Emergency Conductor: 105
Short Circuit Conductor: 250
Minimum Installation: -10
Design Characteristics
Design Standards: AEIC, IEC
Factory Test Voltages (@400 kV): 265 kV / 60 min
XLPE Loss Factor: 0.0005
Relative Permittivity: 2.3
Specifications:
Conductor Size: 1000 MCM
Conductor Dia. (inches): 1.06
Insulation Thickness (mils): 945
Diameter Over Insulation (inches): 3.08
Overall Jacket Diameter (inches): 3.76
Min. Bending Radius (install / perm.) (inches): 68/46
Capacitance (pF/ft): 42.73
Charging Current (A/kft): 2.14
Cable Weight (lbs/ft): 5.95
Ampacity @ 90°C; Single Circuit (Fig 1): 670 Amps
Power Rating: 267 MVA
Ampacity @ 90°C; Double Circuit (Fig 2): 570 Amps
Power Rating: 227 MVA
Call Us: 1-516-482-6313 Text Us: 1-516-703-3460
Garrie AI: Your Cable Guide