500-500-500-350 Wofford Quadruplex Aluminum Conductor Underground Direct Burial 600V URD

Where are we? 4 Continents 8 Countries


Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Quick Support
500-500-500-350 Wofford Quadruplex Aluminum Conductor Underground Direct Burial 600V URD
Allowable Ampacity for 500-500-500-350 Wofford Quadruplex Aluminum Conductor 600V URD direct burial: 467 Amps
Allowable Ampacity for 500-500-500-350 Wofford Quadruplex Aluminum Conductor 600V URD in duct: 420 Amps
Applications:
The 500-500-500-350 Wofford Quadruplex Aluminum URD Cable is designed for secondary power distribution in underground electrical systems. It is 600V-rated and suitable for direct burial or installation in ducts. With high-strength aluminum conductors and XLPE insulation, this cable is moisture-resistant, heat-resistant, and durable for outdoor use.
With a maximum operating temperature of 90°C, it performs reliably in both wet and dry environments. Its pre-pulled duct design allows for easier installation in utility and commercial power distribution systems.
Also Known As:
500-500-500-350 wofford aluminum urd cable, 500-500-500-350 wofford urd direct burial cable, 500-500-500-350 wofford quadruplex cable, 500-500-500-350 wofford quadruplex wire, 500-500-500-350 wofford four conductor wire, 500-500-500-350 wofford four conductor cable, 500-500-500-350 wofford direct burial electrical cable, 500-500-500-350 wofford direct burial power cable, 500-500-500-350 wofford aluminum direct burial cable.
Specific Use Cases of 500-500-500-350 Aluminum URD
This cable is designed for medium to high-load secondary distribution, where 500 MCM conductors provide the necessary ampacity for commercial, utility, and infrastructure applications.
- It distributes secondary power from transformers to service meters in urban grids and industrial zones.
- It supplies underground power to commercial buildings, industrial facilities, and municipal infrastructure.
- It provides power to residential subdivisions and mixed-use developments where underground service is necessary.
- It is used for buried power vaults and substation connections.
- It supports underground power in renewable energy systems, emergency backup grids, and construction site power.
Standards:
-
ASTM B-230
-
ASTM B-231
-
ASTM B-609
-
ASTM B-901
-
ICEA S-105-692
-
Federal Specification J-C – 30B
-
RUS ACCEPTED
Construction
Conductors:
Aluminum conductor used for this cable is either a concentric strand or compressed 1350-H19 series aluminum conductor. The conductors are cabled together, with surface printing for identification. The neutral conductor has a yellow stripe.
Insulation:
Versatile insulation system made of cross linked black polyethylene material helps to secure the cable conductors. This insulation is water tight, repulsive to corrosive substances, resistant to oil, heat and flame. Cross linking a polyethylene helps to achieve an excellent strength that makes the material suitable for covering this cable used in harsh conditions like direct burial installation.
Specifications:
-
Size AWG: 500
-
Stranding: 37
-
Insulation Thickness (mils): 95
-
Neutral Size AWG: 350
-
Single Phase Conductor Inches: 0.990
-
O.D. Inches: 2.390
-
Weight lbs./1000ft: 2251 lbs
-
Ampacity: Direct burial: 467 Amps
-
Ampacity: In duct: 420 Amps