1 1/2" Electri Flexible Conduits Galvanized Steel Type LA Liquidtight Jacket PVC
Where are we? 4 Continents 8 Countries
Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Chat
Live Chat: Bottom Right Corner!
Email Us
info@nassaunationalcable.com
Quick Support
Product Information
Specification
US Trade Size: | 1 1/2" |
ISO: | 50 (mm) |
CSA: | 41 (mm) |
Type: | LA-15 |
Internal Diameter: | Min: 1.575 Inches & Max: 1.600 Inches |
Outer Diameter: | Min: 1.865 Inches & Max: 1.900 Inches |
Inside Bend Radius: | Static: 4.5 Inches & Dynamic: 17.0 Inches |
Weight: | 130.2 Lbs |
Reel 50ft: | Part Gray: 25102 & Part Black: 25802 |
Reel 150ft: |
Part Gray: 25104 & Part Black: 25804 |
1 1/2" Electri Flexible Conduits Galvanized Steel Type LA Liquidtight Jacket PVC
Allowable Ampacity for 1 1/2" Electri Flexible Conduits Galvanized Steel Type LA Liquidtight Jacket PVC: 100 Amps
Application:
This conduit is intended for installation in accordance with Article 350 of the NEC (ANSI/NFPA-70) and in section 14.5.4 of the ANSI/NFPA-79 Standard for Industrial Machinery:
- Listed and marked for Direct Burial and in Poured Concrete
- For containment of 1000 volt and lower potential circuits
- Suitable as a grounding conductor when used for circuits rated up to 20A for the 3/8 & 1/2 inch trade sizes and 60A for the 3/4 through 1-1/4 inch trade sizes in lengths six feet or less per NEC Article 250.118(6). Larger sizes require separate grounding conductor.
- Installations in hazardous (classified) locations:
- Class I Div. 2: Article 501.10 (B)(2) & 501.30 (B)
- Class II Div. 1: Article 502.10 (A)(2) & 502.30 (B) Div. 2: 502.10 (B)(2)
- Class III Div. 1: Article 503.10 (A)(3) & 503.30 (B) Div. 2: 503.10 (B)
- Installed under raised floors in Data Processing Areas Articles 645.5 (E)
- Electric Signs and Outline Lighting over 1000 volts Articles 600.7/600.32(A)(1)
- Permitted for Service Entrance wiring to six feet Article 230.43
- Used as Feeders and Services at Marinas and Boatyards Article 553.7(B)
- Wiring on Building Article 225.10
- Conductor Enclosures Adjacent to Motors over 1000 V Article 430.223
- Underground Service, Feeder, Branch Circuit, and Recreational Vehicle Site Feeder Circuit Conductors Article 551.80
- Elevators and Hoistways Article 620.21
- Pools and Fountains Article 680
- Bodies of water. Article 682
- Fire Pumps. Article 695
This conduit is intended for use according to the Canadian Electrical Code (CEC CSA 22.1-18) as described in clause 12-1300 for dry, damp or wet locations.
- Conforms to CSA C22.2 No. 56-17 Annex A “Heavy Duty”
Hazardous Locations areas where flexibility is necessary:
- Class I Div 2: CSA 22.1 J18-152 (1) (i)
- Class II Div 1: CSA 22.1 J18-204 (4) (b)
- Class II Div 2: CSA 22.1 J18-254 (1) (h)
- Class III Div 1: CSA 22.1 J18-304 (1) (f)
- Class III Div 2: CSA 22.1 J18-354 (h)
- Zone 2: CSA 22.1 18-152 (1) (h)
- Zone 20: CSA 22.1 18-192 (3) (a)
- Zone 21: CSA 22.1 18-202 (4) (a)
- Zone 22: CSA 22.1 18-252 (1) (h)
Also Know As:
Electri Flexible Conduits, Flexible Conduits, Galvanized Steel, Liquidtight Jacket, Type LA Conduits, Jacketed Metallic, Flexible PVC, Flexible Steel Conduit, Heavy-Duty
Type LA
A exible steel conduitwhich is both listed by Underwriters Laboratories Inc. and certied by Canadian Standards Association for“Heavy-Duty” applications. It oers outstanding protection againstwet, oily conditions and is permitted for use in exposed or concealed locations.
Construction:
Inner Core:
- Hot Dipped Galvanized Steel
- 3/8” – 1-1/4” Squarelock Profile with continuous bonding strip
- 1-1/2” – 4” Fully Interlocked Profile
Liquidtight Jacket:
- Flexible PVC
- Resistant to Oils and Mild Acids
- Flame Retardant
- Sunlight Resistant (UV)
- Marked HD for “Heavy-Duty”
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color
Reviews
Call Us: 1-516-482-6313 Text Us: 1-516-703-3460