2 AWG HVTECK Copper 90 mil NLEPR CB AIA 5kV 100% IL Orange PVC Jacket CSA
Application:
The 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant.
Also Known As:
2 AWG HVTECK 5kV Copper Cable, 1/C 90 mil NLEPR Power Cable, Copper Conductor 5kV CSA Cable, 5kV Orange PVC Jacket Cable, 2 AWG AIA Armored Medium Voltage Cable, 5kV Copper Building Wire CSA, 90 mil NLEPR Insulated Cable, 2 AWG CSA Approved 5kV Power Cable, HVTECK Copper 1 Conductor Cable, 5kV Copper Electrical Cable PVC.
Construction:
• Conductor: Class B compressed stranded bare copper per ASTM B3 and ASTM B8
• Conductor Shield: Semi-conducting cross-linked copolymer
• Insulation: 90 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 100% insulation level
• Insulation Shield: Strippable semi-conducting cross-linked copolymer
• Tape Shield: 5 mil tape shield
• Concentric Shield: Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
• Neutral Separator: Mylar tape
• Inner Jacket: PVC inner jacket
• Armour: Aluminum Interlocked Armour (AIA)
• Overall Jacket: Orange Polyvinyl Chloride (PVC) Jacket
Standards:
• ASTM B3 Soft or Annealed Copper Wire
• ASTM B8 Concentric-Lay-Stranded Copper Conductors
• CSA C22.2 No. 174 Cables in Hazardous Locations
• CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
• CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
• CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
• CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
• CSA HL - for Hazardous Locations rating
• CSA SUN RES - for Sunlight Resistant rating
• ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
• ICEA T-29-520 Flame Test (210,000 BTU/Hr)
• IEEE 383 Flame Test (70,000 btu)
• IEEE 1202 FT4 Flame Test (70,000) BTU/hr Vertical Tray Test (1/0 and Larger)
• FT1 Flame Test (1,706 BTU/Hr nominal - Vertical Wire Flame Test)
• AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
Specifications:
• Size: 2 AWG
• Number of Strands: 7
• Diameter Over Conductor (inch): 0.282
• Diameter Over Insulation (inch): 0.500
• Insul. Thickness mil: 90
• Diameter Over Insulation Shield (inch): 0.560
• Concentric Neutral No. x AWG: 7x14
• Inner Jacket Thickness (mil): 65
• Diameter Over Armor (inch): 1.040
• Overall Jacket Thickness mil : 50
• Approx. OD inch : 1.140
• Copper Weight lb/1000ft: 299
• Approx. Weight (Lbs/1000'Ft): 735
• Min Bending Radius (In): 13.7
• DC Resistance @ 25°C Ω /1000ft: 0.162
• AC Resistance @ 90°Ω /1000ft: 0.204
• Inductive Reactance @ 60HzΩ/1000ft: 0.054
• Allowable Ampacity In Air 90°C Amp: 215
• Allowable Ampacity Directly Buried 90°C Amp: 221