2 AWG 3C Stranded Aluminium Shield Overall BC Tape XLPE PVC 12/20KV ARE4H1RX Medium Voltage Cable
Where are we? 4 Continents 8 Countries
Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Chat
Live Chat: Bottom Right Corner!
Email Us
info@nassaunationalcable.com
Quick Support
Product Information
Specification
2 AWG 3C Stranded Aluminium Shield Overall BC Tape XLPE PVC 12/20KV ARE4H1RX Medium Voltage Cable
Allowable Ampacity for 2 AWG 3C Stranded Aluminium Shield Overall BC Tape XLPE PVC 12/20KV ARE4H1RX Medium Voltage Cable:100 Amps
About:
This cable is designed for transmitting electricity at medium voltage levels, specifically rated for 12/20kV. It consists of a 2 AWG (American Wire Gauge) 3-core stranded aluminum conductor, which is suitable for various applications requiring a robust and efficient power delivery system.
Also Known As:
• 2 AWG 3C Aluminum MV cable
• 12/20KV Aluminum shielded cable
• ARE4H1RX medium voltage cable
• Stranded Aluminum XLPE cable
Application:
• Power transmission and distribution in industrial, commercial, and utility applications.
• Suitable for use in substations, power plants, and other settings where medium voltage power is required.
• Can be installed in ducts, direct buried, or on cable trays, depending on the environmental conditions and installation requirements.
Standards:
• IEC 60502-2 for medium voltage extruded insulation power cables.
• Local or national standards relevant to medium voltage power transmission.
Construction:
• Conductor: Stranded Plain Aluminium Conductor Cl.2, Acc. To Iec 60228
• Inner Semi-conductive Layer: Extruded Semi-conducting Compound
• Insulation: Xlpe Compound
• Outer Semi-conductive Layer: Extruded Semi-conducting Compound
• Screen: Red Copper Wires And One Or Two Copper Tape(S) Applied Helically
• Outer Sheath: Red (Ral 3000), Pvc Type Rz
Features:
• According To Iec 60502-2
Specifications:
• AWG No: 2
• No.of cores x cross section n x mm2: 3 x 1 x 35
• Outer-Ø ca.mm ± 10%: 56,1
• Nominal voltage: Uo/U 12/20 kV, Uo/U 18/30 kV
• Test voltage:Uo/U 12/20 kV= 29 kV
Uo/U 18/30 kV = 45 kV
• Temperature range: 0 oC up to + 90 oC
• Max short circuit temperature: + 250 oC
• Min. bending radius: 20 x d
• Max. tensile stress: 60 N/mm2
• Cable weight approx. kg/km: 1930
• Part Number: 48130URL030M64
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color
Download PDF Spec Sheet
Reviews
Call Us: 1-516-482-6313 Text Us: 1-516-703-3460