18 AWG 4T TC FR-EPR Unshielded Triads Overall Shield Instrumentation Cable 600V
Application:
• UL listed and OSHA acceptable. Recognized for use in Class 1 or 2, Division 2 hazardous locations. Suitable for use in cable trays, raceways, ducts and conduits, direct burial or supported by a messenger for use at temperature ratings not exceeding 90°C in wet or dry locations and outdoors where a sunlight resistant rating is required.
• These cables shall conform to (UL) Type TC Power and Control Tray Cables and National Electrical Code Articles 336, 392, 500 and 501. These cables pass the IEEE-383 70,000 BTU flame test, the IEEE 1202 flame test and the ICEA T-90-520 210,000 BTU flame test.
• Designed for control, power, lighting, telemetry, signals and relay or traffic control.
Scope:
This specification covers the minimum construction requirements for triad cable (UL) listed Type TC consisting of Class B stranded annealed tinned copper, insulated with cross-linked polyethylene, cabled together and jacketed overall with a chlorinated polyethylene (CPE) jacket.
Also Known As:
• 18 AWG Instrumentation Cable
• Type TC Cable
• FR-EPR Tray Cable
• Shielded Control Cable
• Shielded Triads Cable
Construction:
CONDUCTORS
Class B (7 wires) annealed tinned copper
INSULATION:
Flame retardant EPR shall be applied concentrically over each conductor and shall
conform to (UL).
DRAIN WIRE:
Class B (7 wires) annealed tinned copper
OVERALL JACKET:
A black, flame, moisture, oil and sunlight resistant chlorinated polyethylene (CPE) jacket meeting the requirements of UL-1277 shall be applied concentrically overall. The physical properties of the jacket comply with Table 50.28 of UL-1581. A high strength nylon yarn rip cord shall be placed under the jacket to facilitate stripping of the jacket.
SHIELDING:
The pairs have an overall shield consisting of a 1.35 mil thickness aluminum/ polyester tape with a 100% coverage and drain wire.
Specifications:
• AWG: 18
• No. of Triads: 4
• Nominal Jacket Thick (In): 0.060
• Nominal Outside Diameter (In): 0.69
• Minimum Bend Radius (In): 8.3
• Maximum Pull Tension (Pounds): 156
• Approx. Weight 1000 FT (Pounds): 209
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color
Download PDF Spec Sheet