14 AWG 7C Copper FR-XLPE CPE Jacket Control Cable 600V
Applications:
The 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10
Also Known As:
14 AWG 7C 600V Control Cable, 14 AWG 7C FR-XLPE Insulated Control Cable, 16/2 CPE Jacketed Control Cable Flame-Retardant XLPE Control Cable, Industrial Control Cable XLPE/PVC Control Cable, Type TC-ER Cable, UL 1277 Cable, 600 Volt Instrumentation Cable.
Construction:
Conductor:
7 strands class B compressed bare copper per ASTM B3 and ASTM B8
Insulation:
Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
Filler:
Polypropylene filler on cables with 5 or less conductors
Binder:
Polyester flat thread binder tape applied for cables with more than 5 conductor
Rip Chord:
Rip chord for ease of jacket removal
Overall Jacket:
Chlorinated Polyethylene (CPE) Jacket
Standards:
• ASTM B3 Standard Specification for Soft or Annealed Copper Wire
• ASTM B8 Concentric-Lay-Stranded Copper Conductors
• UL 1277 Electrical Power and Control Tray Cables
• UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
• ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
• ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
• ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
• IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
• VW-1 (Vertical-Wire) Flame Test
Specification:
• Size: 14 AWG
• Number of Conductors: 7
• Diameter Over Conductor (inch): 0.070
• Insulation Thickness (Mil): 30
• Jacket Thickness (Mil): 45
• Approx. OD (In): 0.479
• Copper Weight (Lbs/1000'Ft): 90
• Approx. Weight (Lbs/1000'Ft): 171
• DC Resistance Ω /1000ft: 2.630
• AC Resistance @ 90°C Ω /1000ft: 3.288
• Min Bending Radius (In): 1.9
• Allowable Ampacity At 60°C: 12
• Allowable Ampacity 75°C: 15
• Allowable Ampacity 90°C: 15