14 AWG 20C Multi-Conductor FR-XLPE LSZH Jacket Control Cable CU 600V
Applications:
The 600 Volt control cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, aerial supported by a messenger, and where superior electrical properties are desired. These cables are capable of operating continuously at the conductor temperature not in excess of 90°C for normal operation in wet and dry locations, 130°C for emergency overload, and 250°C for short circuit conditions. UL rated constructions can be used in Class I, II, and III, Division 2 hazardous locations per NEC Article 501 and 502. UL rated constructions with 3 or more conductors are listed for exposed runs (TC-ER) per NEC 336.10.
Control Cable 600 Volt Copper Conductors, Flame Retardant Cross Linked Polyethylene (FR-XLPE) Insulation SOLONON Low Smoke Zero Halogen (LSZH) Jacket, Control Cable Conductor Identification Method 1 Table 2. Silicone Free
Also Known As:
14 AWG 20C 600V control cable, FR-XLPE insulated cable, LSZH jacket cable, copper control cable, multi-conductor cable, 14 AWG 20C low smoke zero halogen cable, 14 AWG 20C flame retardant cable, tray-rated control cable, 14 AWG 20C industrial control wire, UL 1277 control cable.
Standards:
• ASTM B3 Standard Specification for Soft or Annealed Copper Wire
• ASTM B8 Concentric-Lay-Stranded Copper Conductors
• UL 44 Thermoset-Insulated Wires and Cables
• UL 1277 Electrical Power and Control Tray Cables
• UL 1685 FT4 Vertical-Tray Fire Propagation and Smoke Release Test
• ICEA S-58-679 Control Cable Conductor Identification Method 1 Table 2
• ICEA S-73-532 Standard for Control, Thermocouple Extension and Instrumentation Cables
• ICEA S-95-658 (NEMA WC70) Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy
• IEEE 1202 FT4 Vertical Tray Flame Test (70,000 Btu/hr) and ICEA T-29-520 - (210,000 Btu/hr)
• VW-1 (Vertical-Wire) Flame Test
Construction:
Conductor:
7 strands class B compressed bare copper per ASTM B3 and ASTM B8
Insulation:
Flame Retardant Cross Linked Polyethylene (FR-XLPE), 30 Mils thick for all cable sizes
Filler:
Polypropylene filler on cables with 5 or less conductors
Binder:
Polyester flat thread binder tape applied for cables with more than 5 conductors
Rip Chord:
Rip chord for ease of jacket removal
Overall Jacket:
SOLONON Low Smoke Zero Halogen (LSZH) Jacket
Specifications:
• Size: 14 AWG
• Number of Conductors: 20
• Diameter Over Conductor (inch): 0.070
• Insulation Thickness (Mil): 30
• Jacket Thickness (Mil): 60
• Approx. OD (In): 0.808
• Copper Weight (Lbs/1000'Ft): 256
• Approx. Weight (Lbs/1000'Ft): 475
• Min Bending Radius (In): 3.2
• Allowable Ampacity At 60°C (Amp): 9
• Allowable Ampacity At 75°C (Amp): 11
• Allowable Ampacity 90°C (Amp): 12