Specification
1250 MCM 1C Stranded Aluminium Tape Shield Armour XLPE PE 12/20KV ARE4H5(GS)E Medium Voltage CableAllowable Ampacity for 1250 MCM 1C Stranded Aluminium Tape Shield Armour XLPE PE 12/20KV ARE4H5(GS)E Medium Voltage Cable: 100 Amps
About:
This particular cable is crafted for medium voltage power transmission and distribution, integrating key materials and design features to ensure reliability and safety. It is suitable for fixed installations, typically in power networks, and can be used in various environments, including underground, outdoor, or within cable ducts.
Also Known As:
• 1250 MCM AWG medium voltage aluminium conductor cable
• 12/20kV single-core aluminium tape shielded cable
• ARE4H5(GS)E 1C XLPE PE medium voltage cable
Application:
• Transmission and distribution of power in medium voltage networks
• Infrastructure projects like sub-stations, power plants, industrial sites, and hospitals
• Connection of renewable energy sources to the grid
• Suitable for both urban and rural power distribution networks
Standards:
• IEC 60502-2 or equivalent standards for medium voltage cables
• Applicable local and international standards governing electrical installations and safety
Construction:
• Conductor: Stranded Plain Aluminium Conductor Cl.2, acc. to IEC 60228
• Inner Semi-Conductive Layer: Extruded Semi-Conducting Compound
• Insulation: XLPE compound
• Outer Semi-Conductive Layer: Extruded Semi-Conducting Compound
• Wrapping: Semi-Conductive Watertight Tape
• Screen: Aluminium tape
• Armour: GAALTHERM® 600 (GAALSHOCK technology)
• Outer Sheath: Red (RAL 3000), PE type DMP
Features:
• According to IEC 60502-2
Specifications:
• No. of cores x cross section n x mm²: 1 x 630
• AWG no.: 1250 MCM
• Outer-Ø ca.mm ± 10%: 59,5
• Nominal Voltage: Uo/U 12/20 kV, Uo/U 18/30 kV
• Test Voltage: Uo/U 12/20 kV= 29 kV, Uo/U 18/30 kV = 45 kV
• Max. Operating Voltage: Uo/U 12/20 kV = Um 24 kV, Uo/U 18/30 kV = Um 36 kV
• Temperature range: - 25° C up to + 90° C
• Max short circuit temperature: + 250° C
• Min. Bending Radius: 13 x d
• Cable Weight approx. kg/km: 3310
• Part Number: 48140URL010M75
*Data provided on this page is subject to change based on different manufacturers' variances