1/0 AWG 3C HVTECK Copper 420 mil NLEPR TS AIA 35kV 133% IL Black PVC Jacket CSA

Where are we? 4 Continents 9 Countries


Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Quick Support
1/0 AWG 3C HVTECK Copper 420 mil NLEPR TS AIA 35kV 133% IL Black PVC Jacket CSA
Application:
Southwire's 35kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant 3 Conductor, 420 Mils Tree Retardant Cross Linked Polyethylene, 133% Insulation Level, Tape Shield, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket.
Also known as:
Construction:
Conductor:
Class B compressed stranded bare copper per ASTM B3 and ASTM B8
Conductor Shield:
Semi-conducting cross-linked copolymer
Insulation:
420 Mils Tree Retardant Cross Linked Polyethylene 133% insulation level
Insulation Shield:
Strippable semi-conducting cross-linked copolymer
Copper Tape Shield:
Helically wrapped 5 mil copper tape with 25% overlap
Filler:
Interstices filled with non-hydroscoping/non-wicking fillers
Grounding Conductor:
Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
Binder:
Polypropylene tape
Inner Jacket:
PVC inner jacket
Armour:
Aluminum Interlocked Armour (AIA)
Overall Jacket:
Black Polyvinyl Chloride (PVC) Jacket
Standards:
• ASTM B3 Soft or Annealed Copper Wire
• ASTM B8 Concentric-Lay-Stranded Copper Conductors
• CSA C22.2 No. 174 Cables in Hazardous Locations
• CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
• CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
• CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
• CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
• CSA HL - for Hazardous Locations rating
• CSA SUN RES - for Sunlight Resistant rating
• ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
• ICEA T-29-520 Flame Test (210,000 BTU/Hr)
Specification:
• Size: 1/0 AWG
•Number of conductor: 3
• Number of Strands: 19
• Diameter Over Conductor (inch): 0.361
• Diameter Over Insulation (inch): 1.240
• Insul. Thickness mil: 420
• Diameter Over Insulation Shield (inch): 1.300
• Ground Size AWG: 6
• Inner Jacket Thickness (mil): 125
• Diameter Over Armor (inch): 3.471
• Overall Jacket Thickness mil : 85
• Approx. OD inch : 3.641
• Copper Weight lb/1000ft: 1379
• Approx. Weight (Lbs/1000'Ft): 5319
• DC Resistance @ 25°C Ω /1000ft: 0.102
• AC Resistance @ 90°Ω /1000ft: 0.128
• Allowable Ampacity In Air 90°C Amp: 231
• Allowable Ampacity Directly Buried 90°C Amp: 256