Top 15 Data Center Wire and Cable Products

Data center cabling extends far beyond network connectivity, from 35 kV medium-voltage feeders at the substation to Cat6A at the rack. AI-driven increases in rack density and power demand require larger feeders, more parallel runs, and greater UPS capacity, making cable selection and procurement increasingly critical.

This guide covers 15 core data center wire and cable products, including power distribution, UPS and battery connections, grounding, network infrastructure, and temporary construction power. Each entry explains the cable’s applications.

top 15 data center wire and cable products

Medium-voltage distribution

Power reaches a data center campus at medium voltage, usually 15kV to 35kV. These cables carry it from the utility and the customer substation to the main distribution units, where transformers step it down. NEC Article 311 covers medium-voltage conductors and cable.

1. MV-105 shielded power cable

MV-105 is the standard medium-voltage feeder from the customer substation to the main distribution units. It uses EPR insulation rated for a 105°C conductor temperature, a copper tape shield, and a PVC jacket. The 105°C rating gives it more ampacity headroom than 90°C cable, which matters in underground duct banks and high-ambient runs.

MV-105 comes in 5kV to 35kV ratings, with copper or aluminum conductors in single or 3-conductor designs. Most data center feeders use the 133% insulation level, which is the right choice on systems where a ground fault may not clear within one minute. Low-friction jackets make long pulls through duct banks easier and reduce pulling damage.

Calculate pulling tension and sidewall bearing pressure before ordering MV cable. Long underground duct banks between substations and data center switchgear can exceed mechanical installation limits. Shielded single-conductor MV cables typically require a minimum bending radius of 12 times the overall cable diameter, while maximum allowable sidewall bearing pressure can vary by cable construction. Larger conduit sweeps, intermediate pull points, or lower-friction jackets may be necessary to keep pulling forces within acceptable limits. Verify the manufacturer's pulling tension, bending radius, and sidewall bearing pressure limits before finalizing the cable route.

Protect MV cable against moisture ingress. Specify water-blocked cable for underground feeders exposed to moisture. Inspect end caps upon delivery and reseal cable ends immediately after cutting. Moisture ingress can accelerate water treeing, weakening insulation and shortening cable service life.

Shop MV-105 power cable.

2. MV-90 aluminum power cable

MV-90 is a cost-effective medium-voltage feeder for high-density campus distribution. It uses XLPE insulation rated for 90°C and aluminum conductors, typically 350 to 1000 kcmil at 35kV. Aluminum cuts both material cost and weight on long campus runs between buildings.

MV-90 suits feeders where the load and the installation conditions do not require the extra thermal headroom of MV-105. Designers often pair the two: MV-105 for the hottest, most heavily loaded duct banks and MV-90 for longer, lower-stress runs.

Shop aluminum MV-90 and MV-105 cable

3. URD cable (35kV, full neutral)

URD (underground residential distribution) cable handles underground primary distribution across data center campuses. It has a stranded aluminum conductor, a 133% insulation level, and a full concentric neutral that carries the full phase current. That full neutral makes URD a good fit for utility-style distribution loops that serve several buildings on a single site.

URD is built for direct burial or duct installation, and it is often the first cable a campus needs. The utility or the developer typically runs it before the buildings go up.

Shop 35kV URD cable

Low-voltage building wire for feeders and branch circuits

After the transformers step power down to 480V or 208V, single-conductor building wire carries it through conduit and tray to switchboards, UPS systems, PDUs and branch panels. NEC Table 310.4(A) lists the conductor types and where each may be used, and Table 310.16 sets their capacities.

4. THHN/THWN-2 building wire

THHN/THWN-2 is the most widely used building wire in a data center. It handles branch circuits and feeders in PVC conduit or cable tray throughout the facility. The conductor has PVC insulation under a nylon jacket, rated 600V and 90°C in dry locations as THHN and in wet locations as THWN-2.

The thin insulation lets more conductors fit in each conduit, and the slick nylon jacket makes pulls easier. Copper comes in 14 AWG to 1000 kcmil, and the compact AA-8000 series aluminum alloy, in 6 AWG to 1000 kcmil, is a cost-saving option for larger feeders. THHN/THWN-2 is listed in UL 83.

Shop THHN/THWN-2 building wire

5. XHHW-2 building wire

XHHW-2 is the go-to conductor for critical, heavily loaded feeders. It is frequently specified for conduit runs that serve UPS and PDU equipment and is common in AI data centers. The insulation is cross-linked polyethylene (XLPE), a thermoset that retains its shape under heat and overload rather than softening like PVC.

XHHW-2 is rated 90°C in both wet and dry locations, and some brands carry a dual 600V/1000V rating. XLPE is lead-free and halogen-free, so it releases no acid gas in a fire, which also makes XHHW-2 a common pick for LEED projects. It is listed to UL 44 and comes with copper or aluminum conductors.

Shop XHHW-2 building wire

6. RHH/RHW-2/USE-2 building wire

RHH/RHW-2/USE-2 is a triple-rated copper conductor for below-grade and direct burial runs. As USE-2, it serves as an underground service entrance cable. As RHW-2, it is rated for raceways in wet locations at 90°C.

The XLPE insulation resists moisture, sunlight, and crushing, which suits it to service feeds and underground duct runs between buildings on a campus. It is rated 600V and listed at UL 44 and UL 854. Burial depths follow NEC 300.5.

Shop RHH/RHW-2/USE-2 building wire

Branch circuit and tray cables

Inside the data hall, multiconductor cables replace many single-wire pulls. They come off the reel with every conductor and the ground already connected, which saves labor on hundreds of identical circuits and simplifies data center wire management.

7. MC cable (aluminum armored)

Type MC cable is the standard for data center power whips. Precut MC whips run under raised floors from power distribution cabinets or remote power panels to the racks, and MC also feeds lighting and receptacle branch circuits. Its aluminum interlocked armor protects the conductors in dense server environments, where cables are moved and walked over during changes.

MC cable is rated 600V, comes with copper or aluminum conductors and a ground, and is listed to UL 1569. NEC Article 330 covers Type MC. Article 645 governs wiring under raised floors in IT equipment rooms, and 300.22(C)(1) covers its use in other air-handling spaces.

MC whips can ship pre-assembled: cut to length, fitted with NEMA, pin-and-sleeve or modular connectors, and labeled for each circuit. Pre-assembled whips reduce the number of pulls and reels on-site and speed up rack installs.

Shop MC cable

8. TC-ER tray cable

TC-ER tray cable carries power, control, and signal circuits in data center cable tray, on the data hall floor or overhead. It bundles 3 or 4 conductors into a single PVC jacket, so a crew pulls a single cable from the disconnect to the server instead of several individual conductors. Fewer, larger cables in the tray make data center cable management cleaner and leave room for future circuits.

The ER (exposed run) rating means the cable has passed crush and impact tests for runs where it leaves the tray. The tray cable is rated at 600V and listed to UL 1277, with THHN or XHHW-2 insulation on the inner conductors. NEC Article 336 covers Type TC, and Article 392 covers cable tray systems.

Shop TC-ER tray cable

UPS, battery and switchgear connections

Backup power is what separates a data center from an ordinary commercial building. The connections between batteries, UPS modules, switchgear, and generators require cables that bend into tight spaces and handle high current without overheating.

9. DLO cable

DLO (diesel locomotive) cable is the standard choice for UPS battery banks, prefabricated cable bus and adjustable cable management systems. It has a Class I flexible stranded tinned copper conductor, EPDM insulation and a thermoset CPE jacket. The fine stranding lets crews route it around cabinets and terminate it in crowded battery racks.

DLO is rated 2kV and carries UL RHH/RHW-2, CSA RW90 and MSHA approvals. The RHW-2 rating allows 90°C operation in wet and dry locations, and the FT4 rating slows vertical flame spread. NEC Article 480 covers stationary battery installations.

Shop DLO cable

10. DC power and battery cable

DC power cable connects backup battery systems, VRLA and lithium-ion UPS banks, and DC distribution racks. Battery strings carry high continuous current at low voltage, so conductor size and flexibility matter more than voltage rating. Configurations vary by project, from single flexible conductors to pre-terminated jumpers with lugs.

Lithium-ion UPS systems save floor space but concentrate more current in smaller cabinets, which increases cable sizes. NEC Article 706 covers energy storage systems, and Article 480 covers the batteries themselves.

Shop battery cable

11. Flexible power cable

Flexible power cable with Class K or Class I rope-lay copper stranding handles switchgear lineup interconnections, generator connection boxes, and motor terminals. It holds its shape around tight bends and terminates easily in confined switchgear compartments. Its bend radius is smaller than DLO's.

These cables are often multi-rated THHN/THWN-2, AWM and MTW at 600V, and 1kV versions use XHHE-2 crosslinked insulation. They are a common choice for prefabricated switchgear and skid-mounted power modules. Contact NNC for sizes and availability.

Grounding and data cabling

A data center needs a low-impedance path for fault current and a clean reference for sensitive electronics. It also needs copper data wire between racks for networking and building systems.

12. Bare copper ground wire

Bare copper wire forms the equipment grounding and bonding network, the ground grid under the building, and the lightning protection system. Ground grids tie the building steel, the service, the generators, and the rack bonding network into a single system, so every metal surface sits at the same potential.

Bare copper comes solid or stranded, with tinned versions for corrosive or below-grade locations. It is made into ASTM B3 and B8. NEC Article 250 covers grounding and bonding, and 250.122 specifies the size of equipment grounding conductors.

Shop bare copper wire

13. Cat6A data cable

Cat6A is the copper standard for data center structured cabling and 10GBASE-T networking. It carries horizontal and backbone runs between racks, management networks, and building systems. Cat6A supports 10 Gb/s over the full 100-meter channel.

Data center Cat6A uses 23 AWG, 4-pair solid copper in U/UTP or shielded F/UTP designs. CMP plenum cable goes in air-handling spaces, and CMR riser cable goes in vertical shafts. It meets ANSI/TIA-568.2-D and UL 444, and NEC Articles 800 and 805 cover communications wiring.

Shop Cat6A cable

Temporary power for construction and commissioning

Data centers need temporary power long before the permanent system is live. Crews run tools and lighting during construction, then load banks and test equipment during commissioning. NEC Article 590 covers temporary installations, and Article 400 covers flexible cords and portable power cables.

14. SOOW portable cord

SOOW cord supplies temporary, portable power during construction, commissioning, and testing. Its rubber insulation and jacket resist oil, water and abrasion, so it holds up on an active job site where cords are dragged, rained on and run over. It is rated 600V and stays flexible in cold weather.

Shop SOOW portable cord

15. Type W cable

Type W is the heavy-duty option for temporary and portable power during construction and commissioning. It is rated 2000V, with extra-flexible copper conductors and a tough rubber jacket built for repeated handling. Crews use it for larger temporary feeds, such as portable generators and distribution boxes, where SOOW is too small.

Shop Type W cable

Quick reference

Procurement teams should also check two requirements before ordering. Projects seeking LEED credits often ask for Environmental Product Declarations (EPDs) verified to ISO 14025. Federally funded projects may require Build America, Buy America (BABA) compliance for the cable.

How Nassau National Cable works with data centers

Nassau National Cable is a bulk wire and cable distributor and data center supplier for AI and high-density projects. NNC works with data center owners and operators, EPC and GC firms, procurement teams and infrastructure engineers, either as the primary supplier for full-scope cable delivery or as a pre-approved secondary supplier for backup sourcing and expansion.

  • Volume. Typical orders range from 10,000 to 300,000 feet, with larger quantities available on request. NNC stocks aluminum and copper power cable from multiple manufacturers in four U.S. warehouses.

  • Phased delivery. Shipments follow the build schedule, with phased, staged, and multi-site delivery for multi-phase campuses.

  • Supply continuity. Multi-manufacturer sourcing, split-order fulfillment and backup sourcing keep a project from depending on a single factory.

  • Documentation. Cables ship with full documentation and traceability, aligned with NEC, UL, TIA-942-C, ISO/IEC 11801-5 and ANSI/BICSI 002.

  • Job-site prep. NNC cuts to length, configures custom reels, parallels conductors, and ships pre-terminated assemblies with lugs installed.

  • One contact. A dedicated specialist manages each project from quote to final delivery.

Here are some of our data center projects: On a liquid-cooled AI supercomputing build, NNC served as lead supplier and delivered armored power and tray cables in phases on an aggressive schedule. For a data center equipment manufacturer, NNC stepped in with high-volume copper feeder cable when the original vendor couldn't deliver, keeping the installation moving and avoiding a costly shutdown. These are two examples of NNC's data center projects.

Browse data center wire and cable

 

Сables Featured In This Blog

500 MCM Type UL MV105 Shielded EPR Insulation PVC Jacket 133% Insulation Copper Power Cable 15KV
1/0 AWG Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper Power Cable 24kV / 35kV
4/0 AWG Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper Power Cable 24kV / 35kV
350 MCM Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper Power Cable 24kV / 35kV
750 MCM Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper Power Cable 24kV / 35kV
1000 MCM Type UL MV105 Single Conductor Shielded EPR Insulation PVC Jacket Copper Power Cable 24kV / 35kV
1/0 AWG 3C Aluminum MV-90 Tape Shielded XLPE 133% Insulation 420 mil 35 kV
350 Stranded Aluminum Conductor 35kv Urd - Full Neutral 133%
Aluminum Conductor 15KV URD - Full Neutral 133%
1/0 Stranded Aluminum Conductor 15KV URD - Full Neutral 133%
250 MCM THHN/THWN-2 Aluminum Building Wire PVC Insulation Nylon Jacket 600V
XLP USE-2 RHH RHW-2 COPPER CONDUCTOR BUILDING WIRE
600 MCM XHHW-2 Stranded Copper Building Wire
600 MCM XHHW-2 Stranded Copper Building Wire
Sale price
$24.51
Regular price
$24.51
500 MCM XHHW-2 Stranded Copper Building Wire
500 MCM XHHW-2 Stranded Copper Building Wire
Sale price
$21.29
Regular price
$21.29
4/0 AWG XHHW-2 Stranded Copper Building Wire
4/0 AWG XHHW-2 Stranded Copper Building Wire
Sale price
$8.55
Regular price
$8.55
1/0 AWG XHHW-2 Stranded Copper Building Wire
1/0 AWG XHHW-2 Stranded Copper Building Wire
Sale price
$4.74
Regular price
$4.74
12/2 ISOLATED GROUND TYPE MC LIGHTWEIGHT ALUMINUM INTERLOCKED ARMOR ARMORLITE COPPER CONDUCTOR 600V
12/2 Stranded Metal Clad MC Copper Conductor W/G 600V Aluminum Armored Cable
571-31-3244 C-L-X Type MC-HL (XHHW-2) - 500 MCM AWG - 3 Conductors
Tray Cable Unshielded VNTC TC-ER THHN Insulation PVC Jacket 600V E2
4/0 AWG DLO Cable Extreme Torsion Copper EPR Insulation CPE Jacket RHW 2000 V & RW90 2000 V
DLO DIESEL LOCOMOTIVE CABLE RHH/RHW POWER CABLE
4/0 AWG 2KV DLO Diesel Locomotive Cable RHH/RHW Power Cable
4/0 AWG 2KV DLO Diesel Locomotive Cable RHH/RHW Power Cable
Sale price
$13.78
Regular price
$13.78
2 AWG Type W Single-Conductor Portable Power Cable 2kV
2 AWG Type W Single-Conductor Portable Power Cable 2kV
Sale price
$4.95
Regular price
$4.95
SOOW Yellow Portable Cord - 600V
350 AWG 893 Strands Machine Flex THHN/THWN-2 Copper PVC Power Wire
4/0 AWG 2109 Strand Bare Copper XLPE RW90 Machine Flex Power Wire
TYPE SGR EPDM (RUBBER) JACKET BATTERY CABLE
Battery Bare Copper UL3311 UL3279 Rubber Jacket Cable