Select your reel lengths by filling out the fields below. You may have up to 5 different cuts per order.
X =
TOTAL
=
REEL CUT PRICE
=
Product Information
Specification
About:
The NYCY is a solid bare copper tape shielded PVC (Polyvinyl Chloride) power cable designed for low voltage applications, typically rated at 0.6/1KV (600/1000V). This cable is engineered to provide a high level of protection against electrical interference and to ensure secure power transmission, making it suitable for both indoor and outdoor installations.
Also Known As:
•NYCY power cable •Copper tape shielded power cable •Low voltage shielded PVC cable
Application:
Power cables for energy supply are installed in open air, in underground, in water, indoors and in cable ducts, power station, for industry and distribution boards as well as in subscriber networks, where mechanical damages are not to be expected.
Standards:
• Halogen-Free: Meets standards for low smoke emissions and absence of halogen, making it safer in fire conditions. •Cable Standards: Could comply with specific international standards such as IEC 60502-1 for power cables with extruded insulation rated up to 1kV. • Fire Performance: Likely meets fire performance standards specified for FG7(O)AM1 cables, which include flame retardancy, low smoke emission, and absence of corrosive gases. •Electrical Performance: Designed to operate at 0.6/1KV, meeting electrical standards for insulation and voltage rating.
Construction:
• Conductor: Solid red copper conductor Cl.1, acc. to IEC 60228 DIN VDE 0295 •Insulation: PVC type DIV4 • Colour cores: : acc. to DIN VDE 0293-308, HD 308 S2 from 6 cores black cores with consecutive numbers acc. to EN 50334; green-yellow earth-wire from 3 cores • Stranding: Cores stranded concentrically • Inner sheath: Filler compound • Screen: Red copper wires + red copper tape • Outer sheath: Black (RAL 9005), PVC type DMV5
Features:
• According to DIN VDE 0276 part 603.1, HD 603 S1 and IEC 60502-1 • 7 cores and above cc. to DIN VDE 0276 part 627, HD 627 S1and IEC 6050 • UV resistance
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.