MV-105 AIA Three Conductor Aluminum NL-EPR 133% Insulation PVC Red Jacket 15kV
![MV-105 AIA Three Conductor Aluminum NL-EPR 133% Insulation PVC Red Jacket 15kV](http://nassaunationalcable.com/cdn/shop/files/4-removebg-preview_e9b144a1-0ee9-483a-bc42-2bbfa0b577cd_{width}x.png?v=1739198082)
Select a Gauge
Where are we? 4 Continents 8 Countries
![map](http://nassaunationalcable.com/cdn/shop/t/125/assets/MapDesign1.png?v=141730508087340066881694327314)
![garrie](http://nassaunationalcable.com/cdn/shop/t/125/assets/garrie11.png?v=147058525823915106791694327288)
Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Chat
Live Chat: Bottom Right Corner!
Email Us
info@nassaunationalcable.com
Quick Support
Product Information
Specification
Application:
Type MV-105 Three Conductor Aluminum, 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level, Tape Shield, Aluminum Interlocked Armor (AIA), Polyvinyl Chloride (PVC) Jacket. Silicone Free
Also Known As:
MV-105 Cable, Aluminum NL-EPR Cable, Interlocked Armor Cable, Silicone Free Cable, Armor Cable, MV-105 AIA Cable.
Standards:
• ASTM B801 Concentric-Lay-Stranded Conductors of 8000 Series Aluminum Alloy
• ASTM B836 Compact Rounded Stranded Aluminum Conductors
• UL 1072 Medium-Voltage Power Cables
• UL 1685 Vertical-Tray Fire Propagation and Smoke Release Test
• ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
• AEIC CS-8 Specification for extruded dielectric shielded power cables rated for 5 through 46KV (Qualification Test Requirements)
Features:
• Southwire’s 15KV cables are suited for use in wet and dry areas, conduits, ducts, troughs, trays, direct burial, and where superior electrical properties are desired.
• These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated at -35°C for cold bend when UL listed. Rated at -40°C for cold bend and cold impact and marked with "LTGG" when CSA listed or dual UL/CSA listed.
• For uses in Class I and II, Division 2 hazardous locations per NEC Article 501 and 502.Rated for 1000 lbs./FT maximum sidewall pressure.
Construction:
• Conductor: Class B compact stranded 8000 Series aluminum per ASTM B800 and ASTM B836
• Conductor Shield: Semi-conducting cross-linked copolymer; A conductor separator is used for cable size larger than or equal to 500 Kcmil
• Insulation: 220 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% Insulation Level.
• Insulation Shield: Strippable semi-conducting cross-linked copolymer
• Copper Tape Shield: Helically wrapped 5 mil copper tape with 25% overlap
• Grounding Conductor: Class B compressed stranded bare copper ground per ASTM B3 and ASTM B8
• Filler: Wax paper filler
• Binder: Polypropylene tape
• Armor: Aluminum Interlocked Armor (AIA)
• Overall Jacket: Polyvinyl Chloride (PVC)
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
Download PDF Spec Sheet