HVTECK Copper 1/C 115 mil NLEPR CB AIA 5kV 133% IL Orange PVC Jacket CSA
Application:
The 5kV HVTECK is a CSA armoured cable for industrial and commercial medium voltage applications. Rated FT4, -40°C, Hazardous Locations (HL). These cables are capable of operating continuously at the conductor temperature not in excess of 105°C for normal operation, 140°C for emergency overload, and 250°C for short circuit conditions. Rated for 1000 lbs /FT maximum sidewall pressure. These cables feature sunlight and moisture resistance, exceptional corona resistance, resistance to most chemical soils and acids and are flame retardant Single Conductor, 115 Mils No Lead Ethylene Propylene Rubber (NL-EPR), 133% Insulation Level, Concentric Bond, Polyvinyl Chloride (PVC) Inner Jacket, Aluminum Interlocked Armour (AIA), Polyvinyl Chloride (PVC) Jacket.
Also known as:
HVTECK 1/C Copper Cable, 5kV NLEPR with Orange PVC Jacket HVTECK 1-Conductor Copper Cable, 115 mil NLEPR, 5kV, CSA Rated HVTECK 115 mil Copper Cable, 5kV NLEPR, AIA Orange PVC Jacket 1/C Copper HVTECK Cable, 115 mil, 5kV with Orange PVC Jacket 5kV Copper Cable, 1 Conductor, NLEPR, 115 mil, with AIA Orange PVC Jacket HVTECK 1/C 5kV Copper Cable, CSA Certified, 133% Insulation HVTECK 1-Copper 115 mil 5kV NLEPR Cable, Orange PVC Coating HVTECK 1/C Copper 5kV NLEPR Cable with 133% Insulation, AIA Rating
Construction:
Conductor:
Class B compressed stranded bare copper per ASTM B3 and ASTM B8
Conductor Shield:
Semi-conducting cross-linked copolymer
Insulation:
115 Mils No Lead Ethylene Propylene Rubber (NL-EPR) 133% insulation level
Insulation Shield:
Strippable semi-conducting cross-linked copolymer
Tape Shield:
5 mil tape shield
Concentric Shield:
Concentrically applied copper bond / shield wires. Complies with greater than the minimum requirement as per Table 44, CSA Standard C68.10 and Table 16A, Canadian Electrical Code Part 1
Neutral Separator:
Mylar tape
Inner Jacket:
PVC inner jacke
Armour:
Aluminum Interlocked Armour (AIA)
Overall Jacket:
Orange Polyvinyl Chloride (PVC) Jacket
Standards:
• ASTM B3 Soft or Annealed Copper Wire
• ASTM B8 Concentric-Lay-Stranded Copper Conductors
• CSA C22.2 No. 174 Cables in Hazardous Locations
• CSA C22.2 No. 2556 & No. 0.3 Wire and Cable Test Methods
• CSA C68.10 Shielded Power Cables for Commercial and Industrial Applications - 5 to 46 KV
• CSA C68.3 Shielded & Concentric Neutral Power Cable - 5 to 46 kV
• CSA LTGG [-40°C] - as per C68.10 - for Cold Bend and Impact rating
• CSA HL - for Hazardous Locations rating
• CSA SUN RES - for Sunlight Resistant rating
• ICEA S-93-639 (NEMA WC 74) 5-46 KV Shielded Power Cable
• ICEA T-29-520 Flame Test (210,000 BTU/Hr)
[short]