Specification
Draka Lifeline MC Bare Stranded Copper Unjacketed Two Hour Fire Resistive Cable
Applications:
Lifeline® MC fire resistive cables were designed to meet and have successfully passed the two-hour fire rating certification test per UL 2196, Standard for Tests for Fire Resistive Cables.
Lifeline® MC Cables can be used in the following applications to provide survivability during a fire: - Tall Buildings - Fire Pumps - Emergency Feeder Cables - Ventilating Fans - Stairwell Pressurization - Exit Lighting - Elevators / OEO - Emergency lighting for roadway and transit tunnels when cables include optional LSZH jacket over armor Lifeline® MC Cables are preferred over Mineral Insulated (MI) cables, concrete encasement or the construction of fire rated assemblies based on the facts that Lifeline® MC Cables are less costly and easier to install for many applications. Fire resistive cables are required per NFPA 70/NEC, Articles 517, 695, 700, 708, 728 and 760 as well as NFPA 72 and NFPA 101.
Also Known as:
Metal Clad Cable, Bare Copper Cable, MC Unjacketed Cables, Fire Resistive Cable, Draka Lifeline MC Cable
Specifications and Ratings:
• Listed to UL 1569, Metal Clad Cables, as the following type: • Type MC 600 Volt, Rated 90°C • For Wet Locations • For Cable Tray Use IEEE 1202/ FT4 Rated, ST1 Limited Smoke • Classified to UL 2196, Standard for Tests for Fire Resistive Cables, for two-hours installations • Electrical Circuit Integrity System (FHIT) No. 50 of the UL Fire Resistance Directory • NFPA 70, NFPA 101 compliant • Corrugated Copper Armor meets Equipment Grounding Conductor requirements of NEC Table 250.122
Design Parameters:
• CONDUCTORS: Bare stranded copper, 14 AWG through 600 kcmil • INSULATION: Ceramifiable Silicone Zero Halogen (LSZH) • INNER BINDER JACKET: Ceramifiable Silicone Zero Halogen (LSZH) • ARMOR: Continuously Welded and Corrugated Copper • IDENTIFICATION: Lifeline® MC Unjacketed Cables are marked as follows: DRAKA MA P/N [########] [X]/C [Y] LIFELINE (UL) E66840T MC-ST1 600V 90C WET LOCS FOR CT USE IEEE 1202/FT4 ST1 (UL) R19359 FRR 2HR UL 2196 ELECTRIC CIRCUIT INTEGRITY SYSTEM FHIT#50 480V UTILIZATION (MONTH/YEAR) (SEQUENTIAL FOOTAGE) Notes: [#] is cable part number [X] is the number of conductors [Y] is the size of the cable in AWG or kcmil