Draka LMC041/0 1/0 MCM 4C Lifeline MC Bare Stranded Copper Unjacketed Two Hour Fire Resistive Cable
Where are we? 4 Continents 8 Countries
Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Chat
Live Chat: Bottom Right Corner!
Email Us
info@nassaunationalcable.com
Quick Support
Product Information
Specification
Draka LMC041/0 1/0 MCM 4C Lifeline MC Bare Stranded Copper Unjacketed Two Hour Fire Resistive Cable
Allowable Ampacity for Draka LMC041/0 1/0 MCM 4C Lifeline MC Bare Stranded Copper Unjacketed Two Hour Fire Resistive Cable: 100 Amps
Applications:
Lifeline® MC fire resistive cables were designed to meet and have successfully passed the two-hour fire rating certification test per UL 2196, Standard for Tests for Fire Resistive Cables.
Lifeline® MC Cables can be used in the following applications to provide survivability during a fire: - Tall Buildings - Fire Pumps - Emergency Feeder Cables - Ventilating Fans - Stairwell Pressurization - Exit Lighting - Elevators / OEO - Emergency lighting for roadway and transit tunnels when cables include optional LSZH jacket over armor Lifeline® MC Cables are preferred over Mineral Insulated (MI) cables, concrete encasement or the construction of fire rated assemblies based on the facts that Lifeline® MC Cables are less costly and easier to install for many applications. Fire resistive cables are required per NFPA 70/NEC, Articles 517, 695, 700, 708, 728 and 760 as well as NFPA 72 and NFPA 101.
Also Known as:
Metal Clad Cable, Bare Copper Cable, MC Unjacketed Cables, Fire Resistive Cable, Draka Lifeline MC Cable, LMC041/0
Specifications and Ratings:
• Listed to UL 1569, Metal Clad Cables, as the following type:
• Type MC 600 Volt, Rated 90°C
• For Wet Locations
• For Cable Tray Use IEEE 1202/ FT4 Rated, ST1 Limited Smoke
• Classified to UL 2196, Standard for Tests for Fire Resistive Cables, for two-hours installations
• Electrical Circuit Integrity System (FHIT) No. 50 of the UL Fire Resistance Directory
• NFPA 70, NFPA 101 compliant
• Corrugated Copper Armor meets Equipment Grounding Conductor requirements of NEC Table 250.122
Design Parameters:
• CONDUCTORS: Bare stranded copper, 14 AWG through 600 kcmil
• INSULATION: Ceramifiable Silicone Zero Halogen (LSZH)
• INNER BINDER JACKET: Ceramifiable Silicone Zero Halogen (LSZH)
• ARMOR: Continuously Welded and Corrugated Copper
• IDENTIFICATION: Lifeline® MC Unjacketed Cables are marked as follows: DRAKA MA P/N [########] [X]/C [Y] LIFELINE (UL) E66840T MC-ST1 600V 90C WET LOCS FOR CT USE IEEE 1202/FT4 ST1 (UL) R19359 FRR 2HR UL 2196 ELECTRIC CIRCUIT INTEGRITY SYSTEM FHIT#50 480V UTILIZATION (MONTH/YEAR) (SEQUENTIAL FOOTAGE)
Notes: [#] is cable part number [X] is the number of conductors [Y] is the size of the cable in AWG or kcmil
Specification:
• Size AWG: 1/0
• Number of Cond: 4
• Nominal Core Diameter (in): 1.47
• Nominal Armor Diameter (in): 1.85
• Ampacity* 75°C Amps: 150
• Ampacity* 90°C Amps: 170
• Net Weight: 1.70 lbs per ft
• Part Number: LMC041/0
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color
Reviews
Call Us: 1-516-482-6313 Text Us: 1-516-703-3460