2/0 AWG 3C Solid/Stranded BC Tape Shielded Glass-Fibre Wrap Polymer NHXCH-FE 0.6/1KV Security Cable
Allowable Ampacity for 2/0 AWG 3C Solid/Stranded BC Tape Shielded Glass-Fibre Wrap Polymer NHXCH-FE 0.6/1KV Security Cable: 100 Amps
About:
This cable is configured with a 2/0 American Wire Gauge (AWG) thickness and contains three conductors (3C), making it suitable for more complex electrical circuits that require an additional conductor compared to the 2C variant. It's designed for situations demanding high safety and fire-resistant properties, ensuring operational integrity under extreme conditions.
Also Known As:
• 2/0 AWG: Indicates the gauge size, reflecting the conductor's diameter and current-handling capability.
• 3C: Denotes three conductors within the cable, facilitating more complex or redundant circuit configurations.
• NHXCH-FE: Suggests that the cable is non-halogenated (NH), has fire-resistant characteristics (XCH), and maintains circuit integrity under fire exposure (FE).
Application:
• Critical Infrastructure: Supports systems that must remain operational in emergencies, such as in hospitals, airports, and commercial buildings.
• Emergency Systems: Used in emergency lighting, fire alarm circuits, and backup power systems requiring consistent operation during fires.
• Control Circuits: Powers control panels and safety devices that need to function uninterruptedly during adverse conditions.
• Communication Lines: Ensures the reliability of communication infrastructure within safety-critical environments.
Standards:
• IEC 60331: Tests for electric cables' circuit integrity under fire conditions.
• EN 50200: Specifies performance requirements for maintaining circuit integrity in fire scenarios.
• BS 6387: Defines criteria for cables maintaining circuit integrity under fire, mechanical shock, and water spray conditions.
Construction:
• Conductor: Solid or stranded red copper conductor Cl. 1 or 2, acc. to IEC 60228, DIN VDE 0259
• Insulation: Special core insulation of mica tape and cross-linked polymer type HI1, acc.to DIN VDE 0207 part 23
• Colour cores: acc. to DIN VDE 0293-308, HD 308 S2
• Stranding: Cores stranded in layers
• Wrapping: Glass-fibre
• Screen: Red copper wires and one or two copper tape(s) applied helically
• Outer Sheath: orange (RAL 2003), polymer compound acc. to DIN VDE 0207 part 24, flame retardant orange (RAL 2003), polymer compound acc. to DIN VDE 0207 part 24, flame retardant
Features:
• Security cable, 0,6/1 kV, with improved fire characteristics
• Insulation integrity under flame propagation to VDE 0472 part 814 IEC 60331
• Burning behavior in fire(funtionality) of the complete cable system to DIN 4102 part 12 (30 min.)
• FE 180: insulation integrity for 180 min. Test to DIN VDE 0472 part.814 IEC 60331
• E 30:functionally for 30 min.Test to DIN 4102 part.12
• re: circular solid conductor
• rm: circular stranded conductor
• sm: sector-shaped stranded conductor
• se: sector-shaped solid conductor
Specifications:
• No. of cores x cross section n x mm²: 3x70/35 rm
• AWG no.: 2/0
• Outer-Ø ca.mm ± 10%: 33
• Copper Weight kg/km: 2410
• Nominal Voltage: Uo/U 0,6/1 kV
• Test Voltage: 4 kV
• Temperature Range: - 30° C up to + 70° C
• Min. bending radius: 15 x d
• Radiation Resistance: up to 200x106 cJ/kg
• Cable Weight approx. kg/km: 3800
• Part Number: 49110GG3030M66
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color
Download PDF Spec Sheet
Reviews
Call Us: 1-516-482-6313 Text Us: 1-516-703-3460