135-23-3705 350 MCM 1C Stranded Aluminum Shield EPR Okoguard Okoseal PVC MV-105 345mils 35KV Power Cable
Where are we? 4 Continents 8 Countries
Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Chat
Live Chat: Bottom Right Corner!
Email Us
info@nassaunationalcable.com
Quick Support
Product Information
Specification
135-23-3705 350 MCM 1C Stranded Aluminum Shield EPR Okoguard Okoseal PVC MV-105 345mils 35KV Power Cable
Allowable Ampacity for 135-23-3705 350 MCM 1C Stranded Aluminum Shield EPR Okoguard Okoseal PVC MV-105 345mils 35KV Power Cable:100 Amps
About:
This model features a single-core conductor made from 350 MCM stranded aluminum, known for its good conductivity and flexibility. It is insulated with Ethylene Propylene Rubber (EPR), providing excellent electrical properties and resistance to heat. The cable's aluminum shield helps prevent electromagnetic interference, enhancing its performance in clustered or electrically noisy environments. The outer jacket is made from Polyvinyl Chloride (PVC), known as Okoseal, which offers additional protection against chemical and physical stresses. The cable's total insulation thickness is 345 mils, designed specifically to handle voltages up to 35KV.
Also Known As:
• 350 MCM Single Conductor MV-105 Cable
• 35KV EPR Insulated Aluminum Cable
• Aluminum Conductor 35KV PVC Jacket Cable
Application:
• Okoguard shielded Okoseal Type MV-105 power cables are recommended for use as
feeder circuits, in electric utility generating stations, for distribution circuits, and for
feeders or branch circuits in industrial and commercial installations.
• Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed
to sunlight), in any raceway or underground duct, directly buried if installed in a system
with a grounding conductor in close proximity that conforms with NEC Section 315.36 and 250.4(A)(5), or messenger supported in industrial establishments and electric utilities.
• Sizes 1/0 AWG and larger may also be installed in cable tray as permitted by NEC Section 315.32(3).
Standards:
• ICEA S-93-639/NEMA WC 74: Standard for 5-46KV shielded power cables.
• IEEE 1202/CSA FT4: Standard for flame testing, indicating the cable's resistance to fire.
• UL 1072: Standard for medium voltage power cables, certifying the cable's construction and performance.
Construction:
• Conductor: Aluminum per ASTM B-609, Class B Stranded per B-231.
• Strand Screen: Extruded EPR semiconducting strand screen. Meets or
exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.10 and UL 1072.
• Insulation: Meets or exceeds electrical and physical requirements of ICEA S-93-
639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.10 and UL 1072.
• Insulation Screen: Extruded EPR semiconducting insulation screen applied
directly over the insulation. Meets or exceeds electrical and physical requirements of ICEAS-93-639/NEMA WC74 & S-97-682, AEIC CS8, CSA C68.10 and UL 1072.
• Shield: 5 mil bare copper tape helically applied with 25% minimum overlap.
• Jacket: Meets or exceeds electrical and physical requirements of ICEA S-93-
639/NEMA WC74 & S-97-682, CSA C68.10 and UL 1072 for polyvinyl chloride jackets.
UL listed as Type MV-105, sunlight resistant, and for use in cable tray in
accordance with UL 1072.
CSA C68.10 listed as FT4, SR, LTGG (-40°C), TC (< 500 kcmil) and TC-ER (≥ 500
kcmil).
Features:
• Triple tandem extruded, all EPR system.
• Okoguard cables meet or exceed all recognized industry standards (UL, CSA, AEIC, NEMA/ICEA, IEEE).
• 105°C continuous operating temperature.
• 140°C emergency rating.
• 250°C short circuit rating.
• Passes the Vertical Tray Flame Test requirements of UL 1072 and IEEE 383 and 1202.
• Excellent corona resistance.
• Screens are clean stripping.
• Exceptional resistance to "treeing".
• Exceptional resistance to moisture.
• Resistant to most oils, acids, and alkalies.
• Sunlight resistant.
• For Cable Tray Use.
• Improved Temperature Rating.
• Compact constructions available upon special request.
Specifications:
• Conductor Size AWG: 350 MCM
• Conduit Size Inches (4): 5
• Approx. Dia. over Insulation (in.): 1.42
• Jacket Thickness (- mils): 80
• Approx. O.D. (Inches): 1.67
• Approx. Net Weight: 1504
• Ampacities Conduit in Air (1 ): 350
• Ampacities Underground Duct (2): 330
• Cable Tray(3): 475
• Part Number: 135-23-3705
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color