Insulation
Okonite-FMR is Okonite’s trade name for its heat resistant, mechanically rugged black pigmented ethylene-propylene base insulating compound.
Applications
Okonite-FMR Type RHH or RHW-2 600 Volt Power and Control Cables are recommended for general low voltage power and control applications. Okonite-FMR flame retardant insulated power cables may be used in generating plants, substations and industrial plants. Type RHH or RHW-2 may be used up to 90°C in dry or wet locations. These cables may be installed in wet or dry locations, indoors or outdoors, in raceways, underground ducts, cable tray (size 1/0 AWG and larger per NEC 392) or lashed to a messenger for aerial installation.
Specifications Conductor:Uncoated soft copper per ASTM B-3. Solid per ASTM B-3. Sizes smaller than #8 are compress stranded per ASTM B-8. Sizes #8 and larger are compact stranded per ASTM B-496. Insulation:Meets or exceeds all requirements of ICEA S-95-658, NEMA WC-70, IEEE Standard 383, and UL 44.
Listed by Underwriters Laboratories, Inc. as Type RHH or RHW-2, VW-1.
Product Features
Sizes 1/0 AWG and larger pass the Vertical Tray Flame Test requirements of UL 1581 for use in cable tray.
Passes the ICEA T-29-520 210,000 Btu/hr. vertical tray flame test (sizes 6 AWG and larger).
Passes the IEEE 383 Vertical Tray Flame Test.
Passes the IEEE 1202 Vertical Tray Flame Test. (sizes 1/0 AWG and larger).