1 AWG 1C Non-Shielded EPR 133% Hypalon CSPE Jacket MV-105 Cable 5KV
Where are we? 4 Continents 8 Countries
Got any Questions?
Speak with a real person who will go out of their way to help you!
Call Us: 1-516-482-6313Text Us: 1-516-703-3460
Chat
Live Chat: Bottom Right Corner!
Email Us
info@nassaunationalcable.com
Quick Support
Product Information
Specification
1 AWG 1C Non-Shielded EPR 133% Hypalon CSPE Jacket MV-105 Cable 5KV
Description:
• A. Where NEC jurisdiction applies; as 5,000 volt nonshielded power cable. Type MV-105, for use at conductor temperatures not exceeding 105°C in wet or dry locations. Cables meet requirments of Article 310-6 of the National Electrical Code.
• B. For other applications, as nonshielded power cables for use at 5000 volts 100% insulation level (grounded neutral) and 133% insulation level (ungrounded neutral) under the following conditions: (a) Single conductors mounted on insulation in free air in indoor or outdoor locations.
• Circuit voltages are 2400 volts, 4160 volts and 4800 volts. (b) Random lay singles in metal conduit and nonmetallic conduit in dry locations at circuit voltage of 2400 volts, 4160 volts and 4800 volts, and in damp or wet locations at circuit voltages of 2400 volts and 4160 volts.
• (c) Triplexed singles in metal conduit and nonmetallic conduit in damp or wet locations at circuit voltage of 4800 volts.
• (d) Single conductors or triplexed singles in cable tray, spaced block supports or in messenger supported rings in dry, damp or wet locations at circuit voltages of 2400 volts and 4160 volts.
• (e) Triplexed singles in cable tray, spaced block supports or in messenger supported rings in damp or wet locations at circuit voltage of 4800 volts.
• (f) Single conductors or triplexed singles, aerially, field-spun to grounded messenger in dry, damp or wet locations at circuit voltages of 2400 volts, 4160 volts, and 4800 volts.
Also Known As:
1 AWG Hypalon Jacket Cable, 1 AWG MV Cable, 1 AWG Medium Voltage Cable, 1 AWG CSPE Cable, 1 AWG MV-105 Cable, 1 AWG MV 5K Cable.
Application:
• Listed by Underwriters Laboratories as 5,000 volt nonshielded cable, Type MV-105 per UL Standard 1072
• Conforms to ICEA Pub. No. 539-693 and NEMA Pub. No. WC4 for Ethylene-propylene rubber-insulated Wire and Cable
• Sizes 1/0 and larger pass UL and IEEE Standard 383 ribbon burner flame test and are UL listed for CT use
• Construction: Annealed tinned copper conductor, extruded conductor shield, EPR insulation, discharge and moisture resistant Hypalon jacket, surface printed
Specification:
• Gauge Size: 1
• No Of Strands: 19
• Insulation Thickness: 0.125 Inch
• Jacket Thickness: 0.080 Inch
• Overall Diameter: 0.80 inch
• Net Weight: 480 lbs/mft
• Part No: P05O2
*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color
Download PDF Spec Sheet
Reviews