115-23-2772 4/0 AWG 3 Okopact Bare Copper Shielded Binder Tape Okoguar
nassaunationalcable.com/en-ca/collections/okoguard-bare-copper-shielded-binder-tape-okoclear-ts-mv-105-15kv-power-cable/products/115-23-2772-4-0-awg-3-okopact-bare-copper-shielded-binder-tape-okoguard-okoclear-ts-mv-105-175mils-15kv-power-cable

Items in Cart ()

View cart

115-23-2772 4/0 AWG 3 Okopact Bare Copper Shielded Binder Tape Okoguard Okoclear-TS MV-105 175mils 15KV Power Cable

115-23-2772 4/0 AWG 3 Okopact Bare Copper Shielded Binder Tape Okoguard Okoclear-TS MV-105 175mils 15KV Power Cable
Roll over image to Zoom

115-23-2772 4/0 AWG 3 Okopact Bare Copper Shielded Binder Tape Okoguard Okoclear-TS MV-105 175mils 15KV Power Cable

SKU: 115-23-2772
okoguard-bare-copper-shielded-binder-tape-okoclear-ts-mv-105-15kv-power-cable

Select a Gauge

115-23-2772 4/0 AWG 3 Okopact Bare Copper Shielded Binder Tape Okoguard Okoclear-TS MV-105 175mils 15KV Power Cable
Price:
Regular price
$0.00 /Qty
Sale price
$0.00 /Qty
Shipping Cost Calculated at Checkout. Standard Lead Time is 1 to 6 Business Days.
Free Shipping: On orders above $1000
Quantity must be 1 or more

Enter the required footage in the quantity box - Cut to one length

Customer Reviews

Be the first to write a review
0%
(0)
0%
(0)
0%
(0)
0%
(0)
0%
(0)

Where are we? 4 Continents 8 Countries

map
garrie

Got any Questions?

Speak with a real person who will go out of their way to help you!

Call Us: 1-516-482-6313Text Us: 1-516-703-3460

Chat

Live Chat: Bottom Right Corner!

Email Us

info@nassaunationalcable.com

Product Information

Specification

115-23-2772 4/0 AWG 3 Okopact Bare Copper Shielded Binder Tape Okoguard Okoclear-TS MV-105 175mils 15KV Power Cable

Allowable Ampacity for 115-23-2772 4/0 AWG 3 Okopact Bare Copper Shielded Binder Tape Okoguard Okoclear-TS MV-105 175mils 15KV Power Cable:100 Amps

About:

This cable is a specialized medium voltage power cable from the Okoguard series, designed to efficiently distribute electricity at 15 kilovolts. It is equipped with advanced insulation and shielding technologies, making it suitable for critical power applications. The "4/0 AWG 3" indicates the gauge and conductor count, which is key for specifying the cable's capacity and size.

Also Known As:

 "115-23-2766 4/0 AWG Okoguard MV-105"
 "15KV 3-conductor Okoguard"
 "4/0 AWG 3C MV-105 with Okoclear-TS insulation"

Application:

 Okoguard shielded three conductor Okoclear-TS Type MV-105 power cables are  recommended for distribution circuits, and for feeders or branch circuits in industrial and utility power distribution systems. Type MV cables may be installed in wet or dry locations, indoors or outdoors (exposed to sunlight), in any raceway or underground duct, directly buried, cable tray, or messenger supported in industrial establishments and electric utilities.

Standards:

 IEEE 1202: Flame test (FT4 rating).
 ICEA S-93-639/NEMA WC 74: Specifications for power cables up to 46kV.
 UL 1072: Standard for medium voltage power cables.
 AEIC CS8: Specifications for extruded dielectric shielded power cables.

Construction:

• Conductors: Uncoated copper compact stranded per ASTM B-496.
• Strand Screen: 
Extruded semiconducting EPR strand screen meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74, CSA C68.10 and UL 1072.
 Insulation: Okoguard meets or exceeds the electrical and physical requirements of ICEA S-93-639/NEMA WC74, CSA C68.10 and UL 1072. The insulated conductors are tested in accordance with AEIC CS8.
• Insulation Screen:
 Extruded semiconducting EPR insulation screen per ICEA S-93-639/NEMA WC74, AEIC CS8, CSA C68.10 and UL 1072.
• Shield:
 5 mil uncoated copper tape helically applied with 12.5% nominal overlap
 Phase Identification: Color coded (black, red, blue) polyester ribbon laid longitudinally under the copper tape shield.
 Grounding Conductor: Uncoated copper compact stranded per ASTM B-496 and sized in accordance with UL 1072.
 Assembly: Cabled with fillers and ground wire in the interstices, binder tape overall.
• Jacket:
 Meets or exceeds electrical and physical requirements of ICEA S-93-639/NEMA WC74, CSA C68.10 and UL 1072 for Type II crosslinked polyolefin jackets UL Listed as Type MV-105, sunlight resistant for use in cable tray, and for direct burial in accordance with UL 1072.

Features:

 Triple tandem extruded, all EPR system.
 Complete prepackaged, color coded, factory tested wiring system.
 Passes the UL 1072, IEEE 383 and IEEE
1202/FT4 Vertical Tray Flame Tests.
 Complies with NEC Section 336.36 and is suitable for direct buried when installed in accordance with NEC Sections 250.4(A)(5).
 Minimum installation temperature of -40C.
 Excellent corona resistance.
 Screens are clean stripping.
 Exceptional resistance to “treeing”.
 Improved Temperature Rating.
 UL listed: MV-105, Sunlight Resistant, Cable Tray Use, and Oil Res I & II.

Specifications:

• Conductor Size AWG kcmil: 4/0
• Conductor Size mm²: 107.0

• Approx. Diameter Over Insulation (in):
0.88
• Grounding Conductor Size AWG kcmil: 3
• Grounding Conductor Size mm²: 26.7
• Approx. Core O.D (Inches): 2.04
• Approx. Core O.D (mm): 51.8
• Jacket Thickness (miles): 110

• Jacket Thickness (mm): 2.79
• Approx. OD (in.): 2.29
• Approx. OD (mm): 58.2

• Approx. Net Weight: 4758
• Ampacities  in Cable Tray (2): 360
• Ampacities  in Direct Burial (3): 375
• Part Number: 115-23-2772


*Data provided on this page is subject to change based on different manufacturers' variances
** Images are for display purposes only refer to Product Technical Details for accurate information on the product.
In the case the material only comes in a predetermined color or doesn’t come with any color

Download PDF Spec Sheet

Reviews

Customer Reviews

Be the first to write a review
0%
(0)
0%
(0)
0%
(0)
0%
(0)
0%
(0)
Get in Touch
Live Chat Get replies right away!
Email info@nassaunationalcable.com

Call Us: 1-516-482-6313    Text Us: 1-516-703-3460